2017-11-15 16:12:11.0000011/15/17 TWO (2) SET OF REVISED PLAN FORWARDED TO FIRE
 FOR REVIEW CARRIER ERIC LONGSHORE.
2017-10-25 12:30:17.000001. THE OCCUPANCY FIRE SEPARATION BETWEEN RESIDENTIAL
 AND BUSINESS INCOMPLETE.
 2. PLANS NEED TO DEMONSTRATE FIRE EXTINGUISHER TYPE,
 SIZE AND PLACEMENT.
 3. THE ESCAPE WINDOW ON THE SECOND FLOOR MUST HAVE AT
 MINIMUM:
 * A CLEAR OPENING OF NOT LESS THAN 5.7 FT THE WIDTH
 SHALL BE NOT LESS THAN 20 INCHES
 AND THE HEIGHT SHALL BE NOT LESS THAN 24 INCHES
 *THE BOTTOM OF THE OPENING SHALL BE NOT MORE THAN 44
 INCHES ABOVE THE FLOOR