2017-04-12 09:40:58.00000RECEIVED THREE (3) COPIES OF ADDITIONAL TWO PAGES AS
 REQUESTED BY JBRANCA-SENT TO FIRE CARRIER ERIC
 LONGSHORE.
2017-04-05 09:54:50.00000 
  
  
  
 HIGHLANDS COUNTY BOARD OF COUNTY COMMISSIONERS
 FIRE PREVENTION BUREAU
 6850 WEST GEORGE BOULEVARD
 SEBRING, FL 33875
 PHONE: 863-385-1112
 FAX: 863-402-7404
  
  
  
  
  
 MEMORANDUM
  
 TO: ERIC LONGSHORE, BUILDING OFFICIAL FROM: JAMES E.
 BRANCA, SR., FIRE
 MARSHAL DATE: APRIL 4, 2017
 RE: WATERS EDGE, PROJECT #17030261
  
  
  
  
 I HAVE REVIEWED THESE PLANS FOR CONFORMANCE WITH THE
 FLORIDA FIRE PREVENTION CODE. ALSO I HAVE
 CONDUCTED A SITE VISIT AND HAVE FOUND THE FOLLOWING
 ISSUES:
  
 1. EXTERIOR DOOR BY EXAM ROOM #1 IS PROPOSED TO BE MADE
 NONFUNCTIONAL BY NEW CONSTRUCTION ON THE
 INTERIOR. IF THE DOOR REMAINS IT MUST NOT BE VISIBLE
 FROM EITHER THE INSIDE OR OUTSIDE OF THE
 BUILDING. THERE IS AN EXTERIOR DOOR IN THE REAR OF THE
 BUILDING THAT IS NOT REFLECTED ON THE
 DEMOLITION OR BUILDOUT PLANS. THIS DOOR ALSO WOULD NEED
 TO BE MADE FUNCTIONAL OR BE REMOVED IN ITS
 ENTIRETY.
 2. THE REAR EXIT BY THE LAB DISCHARGES INTO A DRAINAGE
 DITCH.
 3. HALL #120 MAY BE CONSIDERED A DEAD-END CORRIDOR IF
 THE BREAKROOM DOORS ARE CAPABLE OF BEING
 LOCKED. PLEASE DEMONSTRATE LOCKING ARRANGEMENTS OF THE
 BREAKROOM DOORS.
 4. I AM UNSURE WHAT, IF ANY HAZARDS ARE PRODUCED BY THE
 “NEW EWC” LOCATED BY EXAM
 ROOM #1. PLEASE IDENTIFY WHAT THIS EQUIPMENT IS OR
 DOES. PLEASE HAVE THE APPLICANT ADDRESS THESE
 ISSUES.
  
 IF THERE ARE ANY QUESTIONS I CAN BE REACHED AT
 863-385-1112
  