2017-03-16 09:35:06.00000APPROVED, SEPARATE PERMITTING REQUIRED FOR FIRE ALARM
 AND FIRE SPRINKLER SYSTEM.
2017-01-17 16:00:57.00000I HAVE REVIEWED THESE PLANS IN ACCORDANCE WITH THE
 FLORIDA FIRE PREVENTION CODE AND WILL NEED THE
 FOLLOWING ISSUES ADDRESSED:
 1. CHANGE ALL ST. JOHNS COUNTY REFERENCE TO HIGHLANDS
 COUNTY.
 2. THE AUTOMATIC FIRE SPRINKLER SYSTEMS WILL NEED:
  FORWARD FLOW TEST PORT.
  FIRE DEPARTMENT CONNECTION AT THE BACKFLOW
 PREVENTER.
  UPDATED HYDRANT FLOW TEST DATA.
  FULL ENGINEERED PLANS WHICH INCLUDES THE
 LAYOUT, THE EXTENT OF COVERAGE FOR EACH SYSTEM, AND
 COVERAGE FOR THE CONCEALED COMBUSTIBLE SPACES.
  SEPARATELY PERMITTED FOR BOTH ABOVEGROUND AND
 UNDERGROUND WORK.
 3. FIRE ALARM SYSTEM WILL NEED:
  FULL PLANS WHICH INCLUDES THE EXTENT OF
 COVERAGE FOR EACH SYSTEM.
  SEPARATELY PERMITTED.
 4. EMERGENCY LIGHTING TO A PUBLIC WAY.