Plan Review Notes For Permit 16090336
Permit Number 16090336
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2016-10-14 10:25:22.00000I HAVE REVIEWED THESE PLANS FOR COMPLIANCE WITH THE
 FLORIDA FIRE PREVENTION CODE (FFPC) AND HAVE FOUND THE
 FOLLOWING ISSUES:
 1. I AM UNABLE TO DETERMINE THE EXACT OCCUPANCY AND
 USAGE OF THIS PROJECT. THE APPLICATION STATES IT IS A
 42’ X 100’ WAREHOUSE, THE PLANS IN THE DESIGN NOTES
 STATE IT IS A NON-SPRINKLERED MERCANTILE BUSINESS AND
 FURTHER SHOWS A 1050 FT2 OFFICE AND A 3150 FT2 SHOP. IN
 ORDER TO DETERMINE COMPLIANCE WITH THE FFPC I WILL NEED
 TO HAVE THE PROJECT PROPERLY CLASSIFIED AS TO THE TYPE
 OF OCCUPANCY AND THEN THE EXACT USAGE.
 2. THE BUILDING DISCONNECT WILL HAVE TO BE LOCATED
 WHERE THE FIRE DEPARTMENT WILL HAVE ACCESS TO
 DISCONNECT THE ELECTRICAL SERVICE.
 3. THE PLANS SHOW FIRE EXTINGUISHER LOCATIONS; HOWEVER,
 THEY MUST BE SELECTED, DISTRIBUTED, AND INSTALLED FOR
 THE HAZARD THEY ARE TO PROTECT. GUIDANCE MAY BE FOUND
 IN THE FFPC.
 PLEASE HAVE THE ENGINEER OF RECORD ADDRESS THESE ISSUES
 AND INCORPORATE INTO THE CONSTRUCTION DOCUMENTS AND
 PLANS ALL NECESSARY FIRE CODE REQUIREMENTS FOR THE
 INTENDED OCCUPANCY AND USAGE.