Plan Review Notes For Permit 16070276
Permit Number 16070276
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2016-08-17 08:13:46.00000JIMMY SENT EMAIL THAT REVISION WILL SUFFICE FOR FIRE
 REVIEW AND HE IS SENDING STAMPED PLANS BACK.
2016-08-05 14:11:04.00000JIMMY REVIEWED FOR CONFORMANCE WITH THE 2011 NFPA 96,
 STANDARD FOR VENTILATION CONTROL AND FIRE PROTECTION OF
 COMMERCIAL COOKING OPERATIONS, THIS PLAN PROVIDES A
 CODE COMPLIANT CLEARANCE REDUCTION SYSTEM CONSISTING OF
 3M FIRE BARRIER DUCT WRAP 615+ FOR THE HOOD, GREASE
 REMOVAL DEVICES, EXHAUST FAN AND DUCT. HOWEVER, THERE
 ISN'T PROTECTION ON THE COMBUSTIBLE WALL FROM THE
 BOTTOM OF THE HOOD TO THE FLOOR AS REQUIRED IN SECTION
 4.2.4.3.