Plan Review Notes For Permit 16020352
Permit Number 16020352
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2016-03-14 16:23:42.00000REQUIRED INSPECTIONS: FINAL FOR BUILDING. HOOD AND
 AUTOMATIC FIRE EXTINGUISHER REQUIRE SEPERATE
 PERMITTING."SEE ATTACHED MEMO"
 MEMO: (1) EMERGENCY LIGHTING MUST BE PROVIDED TO A
 PUBLIC WAY (2) BUILDING ELECTRICAL DISCONNECT LOCATION
 IS NOT CLEARLY MAKED ON THE PLANS.
 PLEASE HAVE THEM LOCATE IT IN AN AREA ACCESSIBLE TO THE
 FIRE DEPT (3) THE KITCHEN VENTILATION HOOD ALONG WITH
 THE AUTOMATIC FIRE
 EXTINGUISHING SYSTEM WILL REQUIRE SEPARATE PERMITS.
  
2016-03-14 09:45:03.00000TO: ERIC LONGSHORE, BUILDING OFFICIAL
  
 FROM: JAMES E. BRANCA, SR., FIRE MARSHAL
  
 DATE: MARCH 11, 2016
  
 RE: TACO BELL AT SHOPS OF SHELBY, PROJECT #16020352
  
  
  
 I HAVE REVIEWED THESE PLANS FOR CONFORMANCE WITH THE
 FLORIDA FIRE PREVENTION CODE AND HAVE FOUND
 THE FOLLOWING ISSUES:
  
 1. EMERGENCY LIGHTING MUST BE PROVIDED TO A PUBLIC WAY.
 2. BUILDING ELECTRICAL DISCONNECT LOCATION IS NOT
 CLEARLY MARKED ON THE PLANS. PLEASE HAVE THEM
 LOCATE IT IN AN AREA ACCESSIBLE TO THE FIRE DEPARTMENT.
 3. THE KITCHEN VENTILATION HOOD ALONG WITH THE
 AUTOMATIC FIRE EXTINGUISHING SYSTEM WILL REQUIRE
 SEPARATE PERMITS.
  
 I WILL BE SENDING THE PLANS BACK TO YOUR OFFICE TO
 CONTINUE THE PERMITTING PROCESS. PLEASE HAVE THE
 APPLICANT ADDRESS THESE ISSUES PRIOR TO PERMITTING.
  
  
  
 IF THERE ARE ANY QUESTIONS I CAN BE REACHED AT
 863-385-1112
  