Plan Review Notes
Plan Review Notes For Permit 15060369
Permit Number 15060369
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2015-08-20 08:27:26.000001. A SCHEDULE FOR DOOR LOCKS AND LATCHES ARE NOT SHOWN
 ON THE PLANS.
 ? LSC 16.2.2.2.4 DOOR LATCHES. EVERY DOOR LATCH TO
 CLOSETS, STORAGE AREAS, KITCHENS, AND OTHER SIMILAR
 SPACES OR AREAS SHALL BE SUCH THAT CLIENTS CAN OPEN THE
 DOOR FROM INSIDE THE SPACE OR AREA. THE PURPOSE OF THIS
 REQUIREMENT IS TO PREVENT ARRANGEMENTS WHEREBY A CLIENT
 CAN BE TRAPPED IN A SPACE OR AREA. THIS INCLUDES
 EQUIPMENT SUCH AS REFRIGERATORS AND FREEZERS.
 ? LSC 16.2.2.2.5 BATHROOM DOORS. EVERY BATHROOM DOOR
 LOCK SHALL BE DESIGNED TO ALLOW OPENING OF THE LOCKED
 DOOR FROM THE OUTSIDE BY AN OPENING DEVICE THAT SHALL
 BE READILY ACCESSIBLE TO THE STAFF.
 2. THE KITCHEN HOOD ALONG WITH THE AUTOMATIC FIRE
 EXTINGUISHING SYSTEM WILL REQUIRE SEPARATE SUBMITTALS
 FOR PERMITTING.
 3. THE PLANS DO NOT INDICATE DRAFT STOPPING. LSC
 8.6.11
 4. THE BUILDING NEEDS TO HAVE ?R? PLACARDS WHICH
 INDICATE IT HAS A LIGHT-FRAME TRUSS-TYPE CONSTRUCTION.
 RULE 69A-3 F.A.C.
 PLEASE HAVE THE APPLICANT ADDRESS THESE ISSUES BEFORE
 ISSUING THE PERMIT. THIS CAN BE ACCOMPLISHED WITH A
 LETTER FROM THE DESIGN PROFESSIONAL.