Review Stop FIRE
Sequence Number 1
Notes
Date Text
2014-06-06 15:23:04.00000I HAVE REVIEWED THESE PLANS ALONG WITH CONDUCTED A SITE
 VISIT FOR FIRE CODE COMPLIANCE AND HAVE THE FOLLOWING
 CONCERNS:
  
 1. THE INTERIOR FINISHES ARE MADE OF WOOD PANELING.
 2. THE RESIDENTIAL COOKING EQUIPMENT RANGE HOODS HAVE A
 GREASE BUILDUP WHICH DEMONSTRATES THE PRODUCTION OF
 GREASE LADEN VAPORS. IF THIS TYPE OF COOKING CONTINUES
 THEN THEY WILL BE CLASSIFIED AS COMMERCIAL AND NEED TO
 COMPLY WITH NFPA 96, VENTILATION CONTROL AND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS.
 3. ELECTRICAL PANELS ARE LOCATED BEHIND STORAGE IN A
 CLOSET. (SEE PICTURE)
 4. THE PLANS DO NOT SHOW AN OCCUPANT LOAD CALCULATION.
  
  
 PLEASE HAVE THE APPLICANT ADDRESS THESE ISSUES BEFORE
 WE CONTINUE THE PERMITTING PROCESS.
  
  
 THANKS,
  
 JAMES E. BRANCA, SR.
 FIRE MARSHAL