Plan Review Notes
Plan Review Notes For Permit 12070078
Permit Number 12070078
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2012-08-10 10:15:48.00000REC. EMAIL FROM J BRANCA - RELEASED TO PERMIT - PLANS
 APPROVED
2012-07-25 11:30:43.00000JIMMY BRANCA REQUEST FOR ADDITIONAL INFORMATION: 1.
 FIRE EXTINGUISHERS ARE REQUIRED (LSC 38.3.5), 2. EGRESS
 IS NOT ALLOWED THROUGH STORAGE ROOM (LSC 7.5.2.1), 3.
 THE PLANS INDICATE AN ACCESS CARD READER SYSTEM. THERE
 ARE INSUFFICIENT DETAILS TO ENSURE COMPLIANCE WITH THE
 LSC 7.2.1.6.2
 4. INSUFFICIENT DETAIL FOR EGRESS DOORS. (DOOR SIZE
 AND LOCKING/LATCHING HARDWARE) LSC 38.2.2 5. THE
 PLANS DO NOT SHOW ILLUMINATION OF MEANS OF EGRESS TO
 THE EXIT DISCHARGE. LSC 38.2.8. AND LSC 7.8 6. IF
 THERE WILL BE AN HVAC SYSTEM INSTALLED THERE WILL NEED
 TO BE PLANS INDICATING THE SYSTEM WILL COMPLY WITH LSC
 38.5.2 AND LSC 9.2.
2012-07-10 12:21:20.00000SY DID FIRE TRACKING SHEET & TAKING PLANS TO FIRE