Plan Review Notes
Plan Review Notes For Permit 10040140
Permit Number 10040140
Review Stop BUILDING
Sequence Number 1
Notes
Date Text
2010-06-22 10:49:01.00000DOUBLE PLAN REVIEW FEES
2010-05-11 16:35:26.00000TWO BEDROOM :
  
 ON PAGE TS THE GOVERNING CODE & SPECIFICATIONS: NOTE #5
 IS REFERENECING THE 2001 EDITION AND IT SHOULD BE
 2007;
 PAGE A101 UNDER STRUCTURAL NOTES REFERENCE A: SHOULD BE
 FBC2007;
 PAGE A102 BEDROOM # 2 THE WINDOW SIZE IS NOT SHOWN;
 PAGE A201 RECEPTACLE MISSING IN BEDROOM #2 AND LIVING
 ROOM; LIGHT AT FRONT DOOR IS MISSING, EXTERIOR
 RECEPTACLE AT FRONT AND REAR OF HOME IS MISSING;
 NEED PAN DRAIN FOR WATER HEATER
  
 THREE BEDROOM :
  
 ON PAGE TS THE GOVERNING CODE & SPECIFICATIONS NOTE #5
 IS REFERENECING THE WRONG EDITION OF THE BUILDING
 CODE;
 PAGE A101 UNDER STRUCTURAL NOTES REFERENCE A: SHOULD BE
 FBC2007;
 A102 - NO EGRESS IN BEDROOM #3;
 PAGE A201 PAN DRAIN FOR WATER HEATER;
 RECEPTACLES MISSING IN BEDROOM #2 AND #3 AND THE LIVING
 ROOM; LIGHT AT FRONT DOOR IS MISSING, EXTERIOR
 RECEPTACLE AT FRONT AND REAR OF HOME IS MISSING;
 NO SMOKE DETECTORS;
 TWO PANEL LOCATIONS SHOWN;
 PAGE A301 - WALL ANCHORING DETAIL MISSING;
 THREAD ROD SYSTEM ? STRAPS AT OPENINGS, POST ANCHOR
 DETAIL IS MISSING.
  
  
 FOUR BEDROOM :
  
 ON PAGE TS THE GOVERNING CODE & SPECIFICATIONS NOTE #5
 IS REFERENECING THE WRONG EDITION OF THE BUILDING
 CODE;
 PAGE A101 UNDER STRUCTURAL NOTES REFERENCE A: SHOULD BE
 FBC2007
 PAGE A102 - EGRESS IN BEDROOM TWO AND FOUR ARE NOT
 SHOWN;
 ANCHOR POST DETAIL IS MISSING