-     My Account  
   

Log in is not required to search. In the red banner above select: I Want To > Search > Permits

Plan Review Details - Permit 26040830
Plan Review Stops For Permit 26040830
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 04-29-2026 Cont ID  
Sent By cdorman Date 04-29-2026 Time 15:34 Rev Time 0.00
Received By cdorman Date 04-29-2026 Time 10:09 Sent To  
Notes
2026-04-29 15:34:37.00000SHEET PV3: IS A 50A BACKFED BREAKER INTENDED IN THE
 MAIN SERVICE PANEL? (PCS LIMIT = 30A).
 SHEET PV4: THE AC CURRENT LABEL MUST SHOW THE ACTUAL PV
 SYSTEM MAXIMUM CURRENT OUTPUT (PER INSTALLED
 INVERTERS). THE VALUE SHOWN DOES NOT CORRESPOND TO ANY
 SYSTEM PARAMETER.
  
2026-04-29 10:09:45.00000PERMITTING@MYEQUITYSOLAR.COM
 PP INSPECTIONS ONLY, MY AMELIA INC

Copyright © 2008 – THE PLUS SERIES ® – All Rights Reserved