Plan Review Stops For Permit 26040652
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status C Date 04-29-2026 Cont ID  
Sent By cdorman Date 04-29-2026 Time 12:06 Rev Time 0.00
Received By cdorman Date 04-27-2026 Time 15:48 Sent To  
Notes
2026-04-29 12:06:26.00000CONDITIONAL APPROVED SUBJECT TO COMPLIANCE WITH
 EXAMINER COMMENT ON SHEET PV3 REGARDING THE INCLUSION
 OF AN EGC WITH CONDUCTOR ID #3.
2026-04-27 15:48:35.00000REVISED PLANS PERMTTING@MYEQUITYSOLAR.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 04-22-2026 Cont ID  
Sent By cdorman Date 04-22-2026 Time 16:09 Rev Time 0.00
Received By cdorman Date 04-22-2026 Time 12:15 Sent To  
Notes
2026-04-22 16:09:04.00000SHEET PV-3: INSERT PCS INFORMATION IF FUNCTION IS
 INTENDED TO BE USED; OTHERWISE INCREASE CONDUCTOR SIZE
 AND OVERCURRENT PROTECTION RATING ON UTILITY SIDE OF
 ENPHASE CONTROLLER.
 SHEET PV-4: IF PCS FUNCTION IS USED, PROVIDE LABEL
 INDICATING THIS FUNCTION AND MAXIMUM PROGRAMMED CURRENT
2026-04-22 12:16:25.00000PERMITTING@MYEQUITYSOLAR.COM
 PP INSPECTONS ONLY, MY AMELIA INC