Plan Review Stops For Permit 26040601
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status A Date 04-29-2026 Cont ID  
Sent By cdorman Date 04-29-2026 Time 12:04 Rev Time 0.00
Received By cdorman Date 04-27-2026 Time 15:50 Sent To  
Notes
2026-04-27 15:51:04.00000REVISION RECEIVED PERMITTING@MYEQUITYSOLAR.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 04-21-2026 Cont ID  
Sent By cdorman Date 04-21-2026 Time 16:07 Rev Time 0.00
Received By cdorman Date 04-21-2026 Time 10:50 Sent To  
Notes
2026-04-21 16:07:53.00000SHEET PV-1: CHANGE SCOPE OF WORK NOTE TO SHOW
 SUPPLY-SIDE TAP
 SHEET PV-3: CHANGE OCPD RATING IN TABLE TO MATCH THAT
 SHOWN ON THE ONE-LINE DIAGRAM, CONDUCTORS IDENTIFIED AS
 #8 & #10. OCPD = 60A, NOT 50A.
2026-04-21 10:51:00.00000PERMITTING@MYEQUITYSOLAR.COM