-     My Account  
   

Log in is not required to search. In the red banner above select: I Want To > Search > Permits

Plan Review Details - Permit 26040157
Plan Review Stops For Permit 26040157
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status A Date 04-17-2026 Cont ID  
Sent By cdorman Date 04-17-2026 Time 14:18 Rev Time 0.00
Received By cdorman Date 04-16-2026 Time 10:28 Sent To  
Notes
2026-04-21 13:03:10.00000CALLED IN AND GOT PAYMENT AMOUNT.
2026-04-16 10:29:08.00000REVISIONS KARI.W@BETTEREARTH.SOLAR

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 04-07-2026 Cont ID  
Sent By cdorman Date 04-07-2026 Time 14:14 Rev Time 0.00
Received By cdorman Date 04-07-2026 Time 13:15 Sent To  
Notes
2026-04-10 08:53:33.00000NOC IN ONBASE OR BK 3184 PG 869
2026-04-07 14:14:47.00000SHEET 006:
 1] CHANGE NEW PV DISCONNECT OVERCURRENT PROTECTION TO
 35A MAX OR CHANGE CONDUCTOR ID #3 TO MINIMUM #8CU THWN
 2] SHOW GATEWAY AS EXISTING PER SITE DIAGRAM ON SHEET
 003 (CURRENTLY THE GATEWAY AND THE 60A BREAKER WITHIN
 THE GATEWAY ARE LABELED "N")
  
 SHEET 007: SHOW NEW AC CURRENT/VOLTAGE LABEL AT
 15.8A/240V, TO BE AFFIXED TO NEW PV DISCONNECT.
2026-04-07 13:15:54.00000KARI.W@BETTEREARTH.SOLAR

Copyright © 2008 – THE PLUS SERIES ® – All Rights Reserved