Plan Review Stops For Permit 26040050
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status A Date 04-14-2026 Cont ID  
Sent By cdorman Date 04-14-2026 Time 15:14 Rev Time 0.00
Received By cdorman Date 04-14-2026 Time 08:54 Sent To  
Notes
2026-04-15 10:09:19.00000SENT REQUEST FOR PAYMENT
2026-04-14 08:54:17.00000REVISED PLANS KARI.W@BETTEREARTH.SOLAR

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 04-02-2026 Cont ID  
Sent By cdorman Date 04-02-2026 Time 15:38 Rev Time 0.00
Received By cdorman Date 04-02-2026 Time 09:52 Sent To  
Notes
2026-04-02 15:38:04.00000SHEET 006: CHANGE SUPPLY-SIDE TAP CONDUCTORS (ID #4) TO
 MINIMUM #6 CU PER 705.11 (B)
 SHEET 007: SHOW AC CURRENT/VOLTAGE LABEL PER 690.54.
 LABEL #'S 6, 8, & 9 MAY BE REMOVED AS THEY ARE NOT
 APPLICABLE TO THIS INSTALLATION.
2026-04-02 12:33:31.00000NOC IS IN ONBASE OR BK 3183 PG 1105
2026-04-02 09:52:44.00000ROGER.G@BETTEREARTH.SOLAR