-     My Account  
   

Log in is not required to search. In the red banner above select: I Want To > Search > Permits

Plan Review Details - Permit 26030162
Plan Review Stops For Permit 26030162
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 03-05-2026 Cont ID  
Sent By cdorman Date 03-05-2026 Time 17:03 Rev Time  
Received By cdorman Date 03-03-2026 Time   Sent To  
Notes
2026-03-05 17:03:06.000001] PROVIDE SITE DIAGRAM SHOWING LOCATIONS OF ALL
 PROPOSED COMPONENTS. SITE DIAGRAM SHOULD INDICATE
 ENERGY STORAGE SYSTEM DISCONNECTING MEANS ON THE
 EXTERIOR OF THE HOUSE, PERMANENTLY AND EFFECTIVELY
 LABELED AS TO PURPOSE. ENERGY STORAGE DISCONNECTING
 MEANS IS INTENDED TO OPEN ALL UNGROUNDED CONDUCTORS
 FROM THE POWERWALLS SUPPLYING THE BACKUP PANEL.
 2] SHEET PV4: SHOW LABEL IDENTIFYING THE ENERGY STORAGE
 DISCONNECTING MEANS; SHOW AC CURRENT/VOLTAGE LABEL
 INDICATING TOTAL SYSTEM OUTPUT AMPERAGE AND VOLTAGE.

Copyright © 2008 – THE PLUS SERIES ® – All Rights Reserved