Plan Review Details - Permit 26020013
Plan Review Stops For Permit 26020013
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 6 Status A Date 03-18-2026 Cont ID  
Sent By cdorman Date 03-18-2026 Time 15:24 Rev Time 0.00
Received By cdorman Date 03-18-2026 Time 10:32 Sent To  
Notes
2026-03-18 10:33:03.00000REVISED PLANS AORTIZ@SOLARINSTALLERSOFFLORIDA.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 5 Status D Date 03-16-2026 Cont ID  
Sent By cdorman Date 03-16-2026 Time 16:10 Rev Time 0.00
Received By cdorman Date 03-16-2026 Time 12:28 Sent To  
Notes
2026-03-16 16:10:33.00000SHEET E-2: PREVIOUS DEFICIENCIES CORRECTED. CONDUCTORS
 USED FOR SUPPLY-SIDE TAP MUST BE MINIMUM #6 COPPER OR
 #4 ALUMINUM, 705.11 (B).
2026-03-16 12:28:55.00000AORTIZ@SOLARINSTALLERSOFFLORIDA.COM REVISION

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 4 Status D Date 03-13-2026 Cont ID  
Sent By cdorman Date 03-13-2026 Time 16:33 Rev Time 0.00
Received By cdorman Date 03-13-2026 Time 08:30 Sent To  
Notes
2026-03-13 16:33:40.00000SHEET E-2:
 1] WRITTEN NOTE ON PLANS STATES "TAP AT LINE SIDE".
 ONE-LINE DIAGRAM SHOWS FEEDER TAP (ON LOAD SIDE OF MAIN
 BREAKER). CLEARLY INDICATE INTERCONNECTION POINT. IF
 LOAD SIDE TAP, REMOVE NEUTRAL-TO-GROUND BOND LINK IN PV
 DISCONNECT. SEE 250.24.
 2] THE CORRECT SYSTEM CURRENT OUTPUT IS 34.76 AMPS
 (BASED ON 22 384W MICROINVERTERS). SHOW THIS VALUE ON
 THE LABELS, AS REQUIRED BY 690.54. THE 25% DEMAND
 FACTOR GOVERNS THE SIZE OF CONDUCTORS, EQUIPMENT, AND
 OVERCURRENT PROTECTION; IT SHOULD NOT BE INCLUDED IN
 THE ACTUAL CURRENT OUTPUT LABEL. SEE 690.8 (B)(2) &
 690.9 (B).
 3] SHOW THE RAPID SHUTDOWN GRAPHIC LABEL DEPICTED IN
 FIGURE 690.56 (C).
 REFERENCES ARE FROM THE 2020 NEC.
2026-03-13 08:30:32.00000REVISION AORTIZ@SOLARINSTALLERSOFFLORIDA.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 3 Status D Date 03-10-2026 Cont ID  
Sent By cdorman Date 03-10-2026 Time 15:42 Rev Time 0.00
Received By cdorman Date 03-10-2026 Time 12:16 Sent To  
Notes
2026-03-10 15:42:53.00000SHEET SP-1: ITEMS C AND E IN THE CHART ARE REVERSED,
 LOWER LEFT CORNER OF SHEET.
 SHEET E-2:
 1] IN EXISTING MAIN SERVICE PANEL, THE ILLUSTRATED 150A
 BREAKER DOES NOT AGREE WITH THE DESCRIPTION OF A 200A
 MAIN BREAKER BELOW. SPECIFY EXACT EXISTING OR PROPOSED
 MAIN BREAKER.
 2] IN THE PV DISCONNECT, REMOVE THE NEUTRAL-TO-GROUND
 BOND LINK SHOWN. NEUTRAL CANNOT BE RE-GROUNDED BEYOND
 THE SERVICE DISCONNECT IF USING A LOAD-SIDE (FEEDER)
 TAP.
 3] IN THE SAFETY LABELING SECTION (BOTTOM OF SHEET),
 SHOW ACTUAL SYSTEM VALUES ON THE AC CURRENT/VOLTAGE
 LABEL. SHOW CORRECT SYSTEM AC CURRENT OUTPUT ON THE
 "DUAL POWER SOURCES" LABEL TO BE AFFIXED TO THE METER.
  
2026-03-10 12:16:35.00000REVISION AORTIZ@SOLARINSTALLERSOFFLORIDA.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status A Date 02-05-2026 Cont ID  
Sent By cdorman Date 02-05-2026 Time 14:27 Rev Time 0.00
Received By cdorman Date 02-03-2026 Time 10:58 Sent To  
Notes
2026-02-06 12:31:23.00000SENT REQUEST FOR PAYMENT
2026-02-03 10:58:54.00000AORTIZ@SOLARINSTALLERSOFFLORIDA.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status R Date 02-02-2026 Cont ID  
Sent By cdorman Date 02-02-2026 Time 13:37 Rev Time 0.00
Received By cdorman Date 02-02-2026 Time 08:26 Sent To  
Notes
2026-02-02 13:37:08.00000PROVIDE MANUFACTURER'S SPECIFICATION SHEET FOR ENPHASE
 IQ8HC-72-M-DOM-US MICROINVERTER. THE INCLUDED DOCUMENT
 IS NOT FOR THE PLAN-SPECIFIED MICROINVERTER.
2026-02-02 08:26:46.00000AORTIZ@SOLARINSTALLERSOFFLORIDA.COM