Plan Review Stops For Permit 25110433
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status A Date 12-08-2025 Cont ID  
Sent By cdorman Date 12-08-2025 Time 15:49 Rev Time 0.00
Received By cdorman Date 12-04-2025 Time 13:06 Sent To  
Notes
2025-12-11 16:17:02.00000NOC: OR BK 3157 PG 251 [ON BASE]
2025-12-11 09:00:50.00000SENT PAYMENT INFO
2025-12-04 13:06:38.00000REVISED PLANS PERMITS@SUNVENA.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 11-17-2025 Cont ID  
Sent By cdorman Date 11-17-2025 Time 12:13 Rev Time 0.00
Received By cdorman Date 11-17-2025 Time 10:20 Sent To  
Notes
2025-11-17 12:13:07.00000SHEET E-03: SHOW PROPERLY IDENTIFIED DC MAXIMUM SYSTEM
 VOLTAGE LABEL PER 690.53. THE LABEL CURRENTLY INCLUDED
 ON THIS SHEET INDICATES AC VALUES AND IS NOT NECESSARY
 SINCE AN AC CURRENT/VOLTAGE LABEL IS ALSO SHOWN.
 CALCULATE MAXIMUM DC VOLTAGE PER 690.7 AND SHOW THIS
 VALUE ON A LABEL CLEARLY DENOTING THE VALUE AS DC
 VOLTAGE.
 REQUIRED FOR ALL STRING INVERTER SYSTEMS; REFER TO
 EMAIL SENT 11/04/25 FOR MORE INFORMATION.