-     My Account  
   

Log in is not required to search. In the red banner above select: I Want To > Search > Permits

Plan Review Details - Permit 25110152
Plan Review Stops For Permit 25110152
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status A Date 11-25-2025 Cont ID  
Sent By cdorman Date 11-25-2025 Time 16:06 Rev Time 0.00
Received By cdorman Date 11-20-2025 Time 16:01 Sent To  
Notes
2025-11-26 16:24:37.00000SENT PAYMENT INFO
2025-11-20 16:02:04.00000PERMITS@SUNVENA.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 11-10-2025 Cont ID  
Sent By cdorman Date 11-10-2025 Time 12:02 Rev Time 0.00
Received By cdorman Date 11-10-2025 Time 11:55 Sent To  
Notes
2025-11-14 10:16:53.00000PERMITS@SUNVENA.COM
2025-11-10 12:01:56.00000SHEET E-03: SHOW PROPERLY IDENTIFIED DC MAXIMUM SYSTEM
 VOLTAGE LABEL PER 690.53. THE LABEL CURRENTLY INCLUDED
 ON THIS SHEET INDICATES AC VALUES AND IS NOT NECESSARY
 SINCE AN AC CURRENT/VOLTAGE LABEL IS ALSO SHOWN.
 CALCULATE MAXIMUM DC VOLTAGE PER 690.7 AND SHOW THIS
 VALUE ON A LABEL CLEARLY DENOTING THE VALUE AS DC
 VOLTAGE.
 REQUIRED FOR ALL STRING INVERTER SYSTEMS; REFER TO
 EMAIL SENT 11/04/25 FOR MORE INFORMATION.

Copyright © 2008 – THE PLUS SERIES ® – All Rights Reserved