Plan Review Stops For Permit 25100996
Review Stop ADDRESSING ADDRESSING
Rev No 1 Status A Date 11-10-2025 Cont ID  
Sent By cshackel Date 11-10-2025 Time 12:04 Rev Time 0.00
Received By cshackel Date 10-29-2025 Time 14:45 Sent To  
Notes
2025-11-12 10:28:54.00000SENT REQUEST FOR PAYMENT

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status A Date 11-10-2025 Cont ID  
Sent By cdorman Date 11-10-2025 Time 12:30 Rev Time 0.00
Received By cdorman Date 11-10-2025 Time 11:29 Sent To  
Notes
2025-11-10 11:30:07.00000REVISIONS MONICA.ROJAS@MASTEC.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 10-31-2025 Cont ID  
Sent By cdorman Date 10-31-2025 Time 16:36 Rev Time 0.00
Received By cdorman Date 10-29-2025 Time 14:45 Sent To  
Notes
2025-10-31 16:36:30.00000PLANSHEETS E2 & E3: #4 CU AWG GENERATOR FEEDERS ARE
 UNDERSIZED FOR PROPOSED 150A GENERATOR
 BREAKER/GENERATOR RATING. SHOW CORRECT CONDUCTOR SIZES,
 INCLUDING EQUIPMENT GROUNDING CONDUCTOR, TO REFLECT
 CORRECT VALUES PER TABLE 310.16 AND TABLE 250.122.
2025-10-29 14:45:23.00000MONICA.ROJAS@MASTEC.OCM

Review Stop ENGINEER SITE & DRAINAGE FDO
Rev No 1 Status A Date 11-10-2025 Cont ID  
Sent By cshackel Date 11-10-2025 Time 12:04 Rev Time 0.00
Received By cshackel Date 10-29-2025 Time 14:45 Sent To  
Notes
***NONE***

Review Stop ZONING ZONING DEPARTMENT
Rev No 1 Status A Date 11-04-2025 Cont ID  
Sent By cshackel Date 11-04-2025 Time 09:11 Rev Time 0.00
Received By cshackel Date 10-29-2025 Time 14:45 Sent To  
Notes
***NONE***