2025-10-30 15:36:32.00000SHEET E-01: SHOW A DISCONNECTING MEANS BETWEEN THE
 INVERTER/ESS AND THE GATEWAY, OR AN EQUALLY EFFECTIVE
 MEANS OF SHUTTING DOWN ALL EXPORT POWER FROM THE
 INVERTER/ESS TO DE-ENERGIZE THE INTERIOR BRANCH CIRCUIT
 LOADCENTER IN THE EVENT OF A UTILITY OUTAGE. PER 706.15
 (A) AND HIGHLANDS COUNTY FIRE DEPARTMENT, THIS
 DISCONNECTING MEANS MUST BE ON THE EXTERIOR OF THE
 HOUSE, EXTERNALLY OPERABLE, READILY ACCESSIBLE, AND
 EFFECTIVELY LABELED AS TO ITS PURPOSE.