-     My Account  
   

Log in is not required to search. In the red banner above select: I Want To > Search > Permits

Plan Review Details - Permit 25100860
Plan Review Stops For Permit 25100860
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status A Date 11-13-2025 Cont ID  
Sent By cdorman Date 11-13-2025 Time 14:43 Rev Time 0.00
Received By cdorman Date 11-05-2025 Time 13:18 Sent To  
Notes
2025-11-05 13:19:02.00000REVISION RECEIVED FROM PEBBLES@SUNSPEAR.AI

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 10-30-2025 Cont ID  
Sent By cdorman Date 10-30-2025 Time 14:16 Rev Time 0.00
Received By cdorman Date 10-27-2025 Time 08:42 Sent To  
Notes
2025-11-05 09:44:44.00000FULL PAYMENT RECEIVED WITH REFERENCE NUMBER: 16885007
2025-10-30 14:16:41.00000SHEET E002: SHOW EES DISCONNECTING MEANS ADJACENT TO
 SERVICE EQUIPMENT ON EXTERIOR OF HOUSE, 706.15 (A)
 SHEET E003: SHOW SURGE PROTECTIVE DEVICE AT SERVICE,
 ALTERATION OF SERVICE EQUIPMENT, 230.67. SHOW PROPOSED
 MODEL (CURRENT OUTPUT RATING) OF ESS.
 SHEET E005: SHOW LABEL IDENTIFYING ESS DISCONNECTING
 MEANS (SEE SHEET E002 ABOVE)
 SHEET PD006: SPECIFY PROPOSED ESS MODEL (CURRENT OUTPUT
 RATING)
2025-10-27 08:42:56.00000PEBBLES@SUNSPEAR.AI