Plan Review Stops For Permit 25100428
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status D Date 10-24-2025 Cont ID  
Sent By cdorman Date 10-24-2025 Time 15:22 Rev Time 0.00
Received By cdorman Date 10-24-2025 Time 14:55 Sent To  
Notes
2025-10-24 15:22:01.00000SHEET E-01: SHOW SIZE OF EXISTING FEEDER CONDUCTORS
 SUPPLIED BY EXISTING METER-MAIN; SHOW OVERCURRENT
 PROTECTION (MAIN CIRCUIT BREAKER) IN EXISTING
 DOWNSTREAM FEEDER-SUPPLIED PANEL. REFERENCE 705.12
 (B)(3)(6) AND 705.12 (B)(1)(B).
2025-10-24 14:55:20.00000REVISION, ADJUSTED LAYOUT.

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status C Date 10-24-2025 Cont ID  
Sent By cdorman Date 10-24-2025 Time 14:42 Rev Time 0.00
Received By cdorman Date 10-13-2025 Time 14:01 Sent To  
Notes
2025-10-24 15:24:12.00000CONDITIONAL APPROVAL PENDING INSPECTION VERIFICATION OF
 CORRECT OVERCURRENT PROTECTION IN EXISTING
 FEEDER-SUPPLIED PANEL (NOT SHOWN ON PLANS) PER 705.12
 (B)(1).