Plan Review Details - Permit 25100091
Plan Review Stops For Permit 25100091
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 4 Status A Date 12-17-2025 Cont ID  
Sent By cdorman Date 12-17-2025 Time 14:25 Rev Time 0.00
Received By cdorman Date 12-15-2025 Time 08:51 Sent To  
Notes
2025-12-15 08:53:02.00000REVISION RECEIVED, SENT TO CHUCK, SINCE HE HAS BEEN
 DEALING WITH THIS JOB.

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 3 Status D Date 11-14-2025 Cont ID  
Sent By cdorman Date 11-14-2025 Time 16:04 Rev Time 0.00
Received By cdorman Date 11-14-2025 Time 14:28 Sent To  
Notes
2025-11-14 16:03:57.00000THE SUBMITTED PLANS DO NOT REFLECT ANY OF THE
 CORRECTIONS REQUIRED BY THE PREVIOUS REVIEW DATED
 10/31/25. PLANS REMAIN DISAPPROVED PER PREVIOUS
 COMMENTS.
2025-11-14 14:28:55.00000REVISIONS PERMITSARASOTA@FREEDOMFOREVER.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status D Date 10-31-2025 Cont ID  
Sent By cdorman Date 10-31-2025 Time 15:27 Rev Time 0.00
Received By cdorman Date 10-30-2025 Time 12:06 Sent To  
Notes
2025-10-31 15:27:04.000001] ALL PLAN SHEETS WITH RIGHT HAND COLUMN "SYSTEM
 DETAILS": SHOW AC OUTPUT RATING OF PROPOSED TESLA
 POWERWALL. THE SPECIFICATION OF "13.5 KWH" IS NOT
 SPECIFIC TO THE ACTUAL INVERTER OUTPUT.
 2] SHEET PV7: SHOW A LABEL IDENTIFYING THE ENERGY
 STORAGE SHUTDOWN DEVICE. IF THE EXTERNAL SWITCH ON THE
 POWERWALL IS RELIED ON FOR THIS FUNCTION, SHOW THIS
 LABEL ON THE FACE OF THE POWERWALL INDICATING THE
 SWITCH LOCATION
 3] SHEET PV4:
 A. SHOW THE SPD AT THE GATEWAY OR AT THE INTERIOR LOAD
 CENTER, NOT A THE POWERWALL.
 B. SHOW THE ACTUAL OUTPUT RATING OF THE PROPOSED
 POWERWALL. SEE ITEM #1 ABOVE.
 C. SHOW SHUTDOWN DEVICE FOR ENERGY STORAGE SYSTEM
 (POWERWALL). PER 706.15 (A), THERE MUST BE A READILY
 ACCESSIBLE EFFECTIVELY IDENTIFIED DEVICE ON THE
 EXTERIOR OF THE HOUSE TO DISABLE ALL EXPORT POWER FROM
 THE ESS DURING AN EMERGENCY. IT IS ACCEPTABLE TO RELY
 ON THE POWERWALL'S EXTERNAL SWITCH FOR
 THIS FUNCTION IF IT IS EFFECTIVELY LABELED (SEE ITEM #2
 ABOVE)
2025-10-30 12:06:33.00000PERMITSARASOTA@FREEDOMFOREVER.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 10-03-2025 Cont ID  
Sent By cdorman Date 10-03-2025 Time 13:41 Rev Time 0.00
Received By cdorman Date 10-03-2025 Time 09:05 Sent To  
Notes
2025-10-03 13:41:21.000001] ALL PLAN SHEETS WITH RIGHT HAND COLUMN SYSTEM
 DETAILS: SHOW RATING OF TESLA POWERWALL. THE
 DESIGNATION "POWERWALL 3" IS NOT SPECIFIC TO THE
 PROPOSED MODEL RATING.
  
 2] REMOVE SPEC SHEETS FOR POWERWALL 3 EXPANSION
 UNIT/SOLAR SHUTDOWN DEVICE AS THESE COMPONENTS ARE
 SHOWN BEING INCORPORATED INTO THE INSTALLATION.
  
 3] SHEET PV7:
 A. THE VALUE SHOWN ON THE AC CURRENT LABEL IS INCORRECT
 FOR THE PROPOSED STRING INVERTER; CORRECT THIS VALUE TO
 SHOW 32A
 B. SHOW A LABEL INDENTIFYING THE ENERGY STORAGE
 SHUTDOWN DEVICE (SEE ITEM 4 D)
  
 4] SHEET PV4:
 A. SHOW SPD INSTALLATION DUE TO ALTERATION OF SERVICE
 EQUIPMENT
 B. SHOW CORRECT RATING OF OCPD FOR 7.6KW STRING
 INVERTER
 C. SHOW RATING OF TESLA POWERWALL
 D. SHOW SHUTDOWN DEVICE FOR ENERGY STORAGE (EXTERNAL TO
 POWERWALL), SEE 706.15 (A).
 E. CORRECT THE SIZE OF THE SERVICE ENTRANCE CONDUCTORS
 (METER TO GATEWAY)
  
  
  
2025-10-03 09:05:17.00000PERMITSARASTOA@FREEDOMFOREVER.COM