Plan Review Stops For Permit 25100084
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 10-03-2025 Cont ID  
Sent By cdorman Date 10-03-2025 Time 13:36 Rev Time 0.00
Received By cdorman Date 10-02-2025 Time 16:23 Sent To  
Notes
2025-10-03 13:36:50.000001] ALL PLAN SHEETS WITH RIGHT HAND COLUMN SYSTEM
 DETAILS: SHOW RATING OF TESLA POWERWALL. THE
 DESIGNATION "POWERWALL 3" IS NOT SPECIFIC TO THE
 PROPOSED MODEL RATING.
  
 2] REMOVE SPEC SHEETS FOR POWERWALL 3 EXPANSION
 UNIT/SOLAR SHUTDOWN DEVICE AS THESE COMPONENTS ARE
 SHOWN BEING INCORPORATED INTO THE INSTALLATION.
  
 3] SHEET PV7: SHOW A LABEL INDENTIFYING THE ENERGY
 STORAGE SHUTDOWN DEVICE (IN THIS INSTALLATION, THE
 FUSED SWITCH ADJACENT TO THE GATEWAY)
  
  
 4] SHEET PV4:
 A. SHOW RATING OF TESLA POWERWALL
 B. SHOW A #6 CU EQUIPMENT GROUNDING CONDUCTOR WITH THE
 CIRCUIT CONDUCTORS BETWEEN THE GATEWAY AND THE ADJACENT
 FUSED DISCONNECT.
  
  
  
2025-10-02 16:24:07.00000PERMITSARASOTA@FREEDOMFOREVER.COM