Plan Review Stops For Permit 25080358
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 5 Status A Date 09-04-2025 Cont ID  
Sent By cdorman Date 09-04-2025 Time 16:17 Rev Time 0.00
Received By cdorman Date 09-04-2025 Time 10:11 Sent To  
Notes
2025-09-05 08:00:38.00000SENT REQUEST FOR PAYMENT
2025-09-04 10:11:15.00000RECVD DATASHEETS

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 4 Status R Date 08-28-2025 Cont ID  
Sent By cdorman Date 08-28-2025 Time 14:25 Rev Time 0.00
Received By cdorman Date 08-27-2025 Time 13:52 Sent To  
Notes
2025-08-28 14:24:53.00000PLANS APPROVED. SUBMIT SPECIFICATION SHEET(S) FOR TESLA
 INVERTER AND FOR TESLA MCI-2 RAPID SHUTDOWN DEVICE.
 PLEASE SUBMIT ONLY THE REQUESTED DOCUMENTS IN SEPARATE
 PDF FILES; DO NOT RE-SUBMIT ENTIRE PLANSET.

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 3 Status D Date 08-26-2025 Cont ID  
Sent By cdorman Date 08-26-2025 Time 16:20 Rev Time 0.00
Received By cdorman Date 08-25-2025 Time 12:45 Sent To  
Notes
2025-08-26 16:20:28.00000THE DEFICIENCY IDENTIFIED IN THE PREVIOUS REVIEW HAS
 NOT BEEN CORRECTED.
2025-08-25 12:45:36.00000NEW PLANS WERE SUBMITTED ON THE 19TH.
  

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status D Date 08-19-2025 Cont ID  
Sent By cdorman Date 08-19-2025 Time 15:29 Rev Time 0.00
Received By cdorman Date 08-19-2025 Time 13:44 Sent To  
Notes
2025-08-19 15:29:19.00000SHEET PV5: SHOW OVERCURRENT PROTECTION IN PV
 DISCONNECT.
2025-08-19 13:44:51.00000CVC@SUNWAVEENERGY.BIZ

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 08-12-2025 Cont ID  
Sent By cdorman Date 08-12-2025 Time 15:08 Rev Time 0.00
Received By trowe Date 08-19-2025 Time 13:43 Sent To  
Notes
2025-08-12 15:08:42.00000SHEET PV2: PER FBC-R 324.6.2, AN ARRAY OCCUPYING MORE
 THAN 33% OF THE PLAN VIEW TOTAL ROOF AREA WILL REQUIRE
 A MINIMUM 36" CLEAR SETBACK ON BOTH SIDES OF A
 HORIZONTAL RIDGE.
 SHEET PV6: PER 690.53, SHOW A LABEL INDICATING MAXIMUM
 SYSTEM DC VOLTAGE FOR THE PROPOSED INSTALLATION.
2025-08-11 14:59:41.00000SUNWAVEENERGY.BIZ