Plan Review Details - Permit 25080257
Plan Review Stops For Permit 25080257
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 08-11-2025 Cont ID  
Sent By cdorman Date 08-11-2025 Time 09:12 Rev Time 0.00
Received By cdorman Date 08-07-2025 Time 15:39 Sent To  
Notes
2025-08-11 09:12:13.00000RESUBMIT SHEET PV3 ONLY: CHANGE AC CURRENT/VOLTAGE
 LABEL TO SHOW 23.96A.
 THIS LABEL SHOULD INDICATE THE MAXIMUM SYSTEM RATED AC
 CURRENT OUTPUT WITHOUT BEING MODIFIED BY THE 25% DEMAND
 FACTOR, SEE 690.54.