-     My Account  
   

Log in is not required to search. In the red banner above select: I Want To > Search > Permits

Plan Review Details - Permit 25070038
Plan Review Stops For Permit 25070038
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status A Date 07-24-2025 Cont ID  
Sent By cdorman Date 07-24-2025 Time 15:24 Rev Time 0.00
Received By cdorman Date 07-10-2025 Time 10:45 Sent To  
Notes
2025-07-25 08:44:09.00000SENT REQUEST FOR PAYMENT
2025-07-10 10:46:14.00000REVISED PLAN PERMITTING@MYEQUITYSOLAR.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status R Date 07-02-2025 Cont ID  
Sent By cdorman Date 07-02-2025 Time 12:59 Rev Time 0.00
Received By cdorman Date 07-01-2025 Time 16:49 Sent To  
Notes
2025-07-02 12:59:03.00000SHEET PV3:
 1] PLANS INDICATE PROPOSED METER-MAIN WITH A
 SUPPLY-SIDE TAP; SHOW INTENDED METHOD OF CONNECTION FOR
 THIS TAP. IF USING LOAD-SIDE (FEEDER) TAP, SHOW
 COMPLIANCE WITH 705.12 (B)(1)(B) FOR EXISTING
 FEEDER-SUPPLIED LOAD CENTER AND SHOW COMPLIANCE WITH
 THE LABELING REQUIREMENTS OF 705.12 (B)(3)(3) FOR THE
 PROPOSED METER-MAIN.
 2] SHOW THE INSTALLATION OF AN SPD AT THE NEW SERVICE
 EQUIPMENT PER 230.67.
2025-07-01 16:50:08.00000PERMITTING@MYEQUITYSOLAR.COM
  