Plan Review Stops For Permit 25060446
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status A Date   Cont ID  
Sent By   Date 09-05-2025 Time   Rev Time 0.00
Received By amhernan Date 08-22-2025 Time 14:49 Sent To  
Notes
2025-07-11 15:35:15.00000PERMIT PACKET RETURNED TO CONTRACTOR TO PREPARE
 ENGINEERED PLANS

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status R Date 06-18-2025 Cont ID  
Sent By amhernan Date   Time   Rev Time 0.00
Received By amhernan Date 06-18-2025 Time 11:45 Sent To  
Notes
2025-06-20 15:56:43.00000PLANS ARE INCOMPLETE. SUBMITTAL WILL REQUIRE,
 1. A LIFE SAFETY PAGE INCLUDING BUT NOT LIMITED TO ,
 EXIT TRAVEL DISTANCES, FIRE EXTINGUISHER LOCATIONS,
 EMERGENCY LIGHTING.
 2. ELECTRICAL PAGES INCLUDING PANEL LOCATION AND
 ELECTRICAL DEVICE LOCATIONS.
 3. A PLUMBING PAGES SHOWING NEW PLUMBING ADDITIONS AND
 CONNECTION TO EXISTING SYSTEMS.
 4. PLUMBING DETAIL PAGE SHOWING ADA REQUIREMENTS FOR
 PLUMBING FIXTURES AND CLEARANCES.
 5. A SPRINKLER PLAN SHOWING NEW SPRINKLER HEAD
 LOCATIONS TO PROVIDE COMPLIANT COVERAGE OF NEW ENCLOSED
 ROOM AREAS.
 6. MECHANICAL PAGES IF THE AIR SYSTEMS ARE BEING
 MODIFIED FOR NEW ROOMS.
  
  

Review Stop CONCURRENC CONCURRENCY
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By hlopez Date 07-09-2025 Time 15:37 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status C Date 09-19-2025 Cont ID  
Sent By amhernan Date 09-19-2025 Time 09:18 Rev Time 0.00
Received By amhernan Date 08-22-2025 Time 14:00 Sent To  
Notes
2025-09-19 09:20:24.00000APPROVED AS NOTED
 FIRE ALARM IS REQUIRED – SUBMIT PLANS FOR FIRE ALARM
 SPRINKLER PLANS NOT REQUIRED – VERIFY PROPER COVERAGE
 ON FINAL INSPECTION IF COVERAGE IS GOOD HEADS MY NEED
 TO BE ADDED.
 ONE OF THE RESTROOMS DOES NOT SHOW EMERGENCY LIGHT –
 ADD EMERGENCY LIGHT
 FIRE EXTINGUISHERS ARE NOT SHOWN ON THE PLANS –
 EXTINGUISHER AT EXITS AND WHERE THOSE ARE NOT ABLE TO
 BE REACHED AT 75 FEET
 SIZE OF THE PLANS WAS HARD TO READ. IN THE FUTURE, SEND
 IN LARGER PLANS AND DIGITAL PLANS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status D Date 07-09-2025 Cont ID  
Sent By hlopez Date 07-09-2025 Time 15:16 Rev Time 0.00
Received By hlopez Date 06-18-2025 Time 11:45 Sent To  
Notes
2025-07-09 15:29:39.00000PLAN REVIEW #: 25060446
 PROJECT: REMODEL 58 & 59
 LOCATION: 901 (815) US 27 N, SEBRING, FL 33876
 OCCUPANCY: DAY CARE - ADULT
 REVIEWED BY: JASON RAPER, DIVISION CHIEF FIRE MARSHAL
 DATE: 7/1/25
 PLANS WERE REVIEWED UTILIZING THE FLORIDA FIRE
 PREVENTION CODE (FFPC), FLORIDA STATUTE, FLORIDA
 ADMINISTRATIVE RULE, AND ANY REFERENCE NFPA CODE OR
 STANDARD.
 _______________________________________________________
 _____________________
 DENIED –
 CORRECT PLANS AS INDICATED ON PLANS:
 • MOVE AND ADD FIRE EXTINGUISHERS TO EXITS
 • SPRINKLER HEADS MISSING IN CLOSETS
 • ADD EMERGENCY LIGHTS FOR COVERAGE
 • WALL REMOVAL AND WALL ADDITIONS WILL SHOW IN THE
 LISTED PLANS BELOW
 PLANS NEEDED:
 • PLANS FOR UNITS BEFORE REMODEL, PLANS OF WHAT IS
 BEING REMOVED, PLANS OF THE CHANGES
 • ELECTRICAL PLANS
 • MECHANICAL PLANS
 • PLUMBING PLANS
 • FIRE ALARM PLANS
 • SPRINKLER PLANS
 REVIEW FEE – $400 + INSPECTION FEE $50 = $450