-     My Account  
   

Log in is not required to search. In the red banner above select: I Want To > Search > Permits

Plan Review Details - Permit 25060069
Plan Review Stops For Permit 25060069
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status A Date 06-23-2025 Cont ID  
Sent By elongsho Date 06-23-2025 Time 16:31 Rev Time 0.00
Received By elongsho Date 06-03-2025 Time 11:11 Sent To  
Notes
2025-06-03 11:16:51.00000NEED:
 NOC
 AUTHORIZATION LETTER FROM OWNER

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status C Date 06-23-2025 Cont ID  
Sent By hlopez Date 06-23-2025 Time 09:03 Rev Time 0.00
Received By hlopez Date 06-03-2025 Time 11:11 Sent To  
Notes
2025-06-23 09:03:58.00000PLAN REVIEW #: 25060069
 PROJECT: ADVENT INTERNAL MEDICINE
 LOCATION: 4421 SUN N LAKE
 OCCUPANCY: MEDICAL OFFICE
 REVIEWED BY: JASON RAPER, DIVISION CHIEF FIRE MARSHAL
 PLANS WERE REVIEWED UTILIZING THE FLORIDA FIRE
 PREVENTION CODE (FFPC), FLORIDA STATUTE, FLORIDA
 ADMINISTRATIVE RULE, AND ANY REFERENCE NFPA CODE OR
 STANDARD.
 _______________________________________________________
 _____________________
 APPROVED AS NOTED BELOW AND ON PLANS
 NEED TO ADD EMERGENCY LIGHTS FOR COVERAGE – ALL EXAM
 ROOMS WITHOUT WINDOWS, STAFF LOCKER ROOM, WORKSTATION,
 NURSE STATION, LAB, SPECIMEN TOILET, AND HALLWAY
 EXIT SIGN MISSING ON PLANS AT DOOR BETWEEN 139-140
 TABLE SHOWS 3 EXTINGUISHERS PROVIDED BUT THE PLANS HAVE
 4 EXTINGUISHERS
 THE TITLE PAGE HAS ADDRESS AS SUN N FUN BLVD
 ELECTRICAL PANELS NEED TO BE LABELED FOR EXIT SIGNS AND
 EMERGENCY LIGHTS
 REVIEW FEE – $400 + INSPECTION FEE $50 = $450