-     My Account  
   

Log in is not required to search. In the red banner above select: I Want To > Search > Permits

Plan Review Details - Permit 25050858
Plan Review Stops For Permit 25050858
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status A Date 07-08-2025 Cont ID  
Sent By cdorman Date 07-08-2025 Time 15:47 Rev Time 0.00
Received By cdorman Date 06-30-2025 Time 15:59 Sent To  
Notes
2025-07-10 13:00:12.00000SENT REQUEST FOR PAYMENT
2025-06-30 13:26:47.00000REVISED PLAN WITH REVEIW COMMENTS RECEIVED FROM
 MJEAN-BAPTISTE@SBASITE.COM AND FORWARDED TO C.DORMAN

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 06-05-2025 Cont ID  
Sent By cdorman Date 06-05-2025 Time 13:57 Rev Time 0.00
Received By cdorman Date 05-28-2025 Time 16:35 Sent To  
Notes
2025-06-05 13:57:53.00000SHEET E-1: CONDUIT/CONDUCTOR CALLOUT #4 (CONDUCTORS
 FROM GENERATOR TO ATS ON THE DIAGRAM CIRCUIT SCHEDULE)
 SHOWS #12 AWG CONDUCTORS AND A FUNCTION DESIGNATION OF
 GFCI CIRCUIT. SHOW AS (3) #6 AWG WITH #10 EGC PER THE
 DIAGRAM ON SHEET E-2 AND IDENTIFY FUNCTION AS GENERATOR
 FEEDERS.
 SHOW GENERATOR START/CONTROL CONDUIT AND CONDUCTORS ON
 THIS SHEET.
  
  
 SHEET E-2: SHOW GENERATOR START/CONTROL CONDUIT AND
 CONDUCTORS
  
  
  
  
  
  
  
  
2025-05-28 16:37:05.00000MJEAN-BAPTISTE@SBASITE.COM

Copyright © 2008 – THE PLUS SERIES ® – All Rights Reserved