Plan Review Details - Permit 25050852
Plan Review Stops For Permit 25050852
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status A Date 06-12-2025 Cont ID  
Sent By cdorman Date 06-12-2025 Time 15:14 Rev Time 0.00
Received By cdorman Date 06-12-2025 Time 14:47 Sent To  
Notes
2025-06-20 10:38:43.00000SENT REQUEST FOR PAYMENT
2025-06-12 14:48:04.00000REVISED PLAN WITH REVIEW COMMENTS RECEIVED FROM
 MJEAN-BAPTISTE@SBASITE.COM AND FORWARDED TO C.DORMAN

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 06-05-2025 Cont ID  
Sent By cdorman Date 06-05-2025 Time 13:56 Rev Time 0.00
Received By cdorman Date 05-28-2025 Time 16:34 Sent To  
Notes
2025-06-05 13:56:20.00000SHEET E-1: CONDUIT/CONDUCTOR CALLOUT #4 (CONDUCTORS
 FROM GENERATOR TO ATS ON THE DIAGRAM CIRCUIT SCHEDULE)
 SHOWS #12 AWG CONDUCTORS AND A FUNCTION DESIGNATION OF
 GFCI CIRCUIT. SHOW AS (3) #6 AWG WITH #10 EGC PER THE
 DIAGRAM ON SHEET E-2 AND IDENTIFY FUNCTION AS GENERATOR
 FEEDERS.
 SHOW GENERATOR START/CONTROL CONDUIT AND CONDUCTORS ON
 THIS SHEET.
  
  
 SHEET E-2: SHOW GENERATOR START/CONTROL CONDUIT AND
 CONDUCTORS
2025-05-28 16:37:26.00000MJEAN-BAPTISTE@SBASITE.COM