Plan Review Details - Permit 25050737
Plan Review Stops For Permit 25050737
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status C Date 06-12-2025 Cont ID  
Sent By cdorman Date 06-12-2025 Time 15:44 Rev Time 0.00
Received By cdorman Date 05-23-2025 Time 08:17 Sent To  
Notes
2025-06-12 15:44:50.00000CONDITIONAL APPROVAL SUBJECT TO THE FOLLOWING ITEMS TO
 BE VERIFIED AT INSPECTION:
 1] INSTALL SURGE PROTECTIVE DEVICE AT SERVICE PER
 230.67 (ALTERATION OF SERVICE EQUIPMENT)
 2] PROVIDE, ON THE EXTERIOR OF THE STRUCTURE, READILY
 ACCESSIBLE AND IDENTIFIABLE MEANS OF DISCONNECTING ALL
 ALTERNATE SOURCES OF POWER BY ONE OF THE FOLLOWING
 MEANS:
 A. SIGNAGE ON THE FRONT OF THE GATEWAY DOOR DIRECTING
 USERS TO EMERGENCY SHUTDOWN PROCEDURE
 B. INSTALLATION OF AN E-STOP SWITCH ADJACENT TO THE
 GATEWAY, INCLUDING THE NECESSARY SIGNAGE
 C. A RATED DISCONNECTING DEVICE WITH AN EXTERNALLY
 OPERABLE HANDLE SCHEMATICALLY POSITIONED BETWEEN THE
 GATEWAY AND THE POWERWALL.