Plan Review Details - Permit 25050230
Plan Review Stops For Permit 25050230
Review Stop ADDRESSING ADDRESSING
Rev No 1 Status X Date   Cont ID  
Sent By   Date 06-03-2025 Time   Rev Time 0.00
Received By cshackel Date 05-07-2025 Time 15:37 Sent To  
Notes
***NONE***

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status A Date 05-21-2025 Cont ID  
Sent By elongsho Date 05-21-2025 Time 16:16 Rev Time 0.00
Received By elongsho Date 05-07-2025 Time 15:37 Sent To  
Notes
***NONE***

Review Stop ENGINEER SITE & DRAINAGE FDO
Rev No 1 Status A Date   Cont ID  
Sent By   Date 05-07-2025 Time   Rev Time 0.00
Received By cshackel Date 05-07-2025 Time 15:37 Sent To  
Notes
2025-05-07 15:41:19.0000024120003

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status A Date 06-23-2025 Cont ID  
Sent By hlopez Date 06-23-2025 Time 08:59 Rev Time 0.00
Received By hlopez Date 06-03-2025 Time 08:26 Sent To  
Notes
2025-06-24 08:33:07.00000HARD COPIES STAMPED
2025-06-23 09:00:26.00000PLAN REVIEW #: 25050230
 PROJECT: STEEL BLUE FABRICATION
 LOCATION: 780 CR 17 A
 OCCUPANCY: INDUSTRIAL
 REVIEWED BY: JASON RAPER, DIVISION CHIEF FIRE MARSHAL
 DATE: 6/3/25
 PLANS WERE REVIEWED UTILIZING THE FLORIDA FIRE
 PREVENTION CODE (FFPC), FLORIDA STATUTE, FLORIDA
 ADMINISTRATIVE RULE, AND ANY REFERENCE NFPA CODE OR
 STANDARD.
 _______________________________________________________
 _____________________
 APPROVED – BUILDING, FIRE ALARM AND SPRINKLER PLANS –
 THEY NEED PERMIT NUMBERS
 – ONLY ONE PERMIT NUMBER (PLANS HAS BUILDING,
 SPRINKLER, AND FIRE ALARM INCLUDED)
 REVIEW FEE – $400 + INSPECTION FEE $50 = $450 BUILDING
 PLANS
 $141 + INSPECTION FEE $50 = $191 SPRINKLER PLANS
 $107 + INSPECTION FEE $50 = $157 FIRE ALARM PLANS
 BUILDING PLANS – COMMENTS LABEL BREAKERS THAT EXIT
 SIGNS AND EMERGENCY LIGHTS ARE
 SPRINKLER PLANS – PLANS ARE GOOD
 FIRE ALARM – PLANS ARE GOOD
2025-06-05 12:20:08.00000ADDITIONAL PLANS WERE EMAILED 6-4 BY
 LUPE@COOLANDCOBB.COM
2025-06-03 12:30:01.00000JASON APPROVED FIRE ALARM AND SPRINKLER BUT THEY NEED
 THE APPLICATIONS. APPLIED UNDER BUILDING PERMIT.
2025-06-03 08:32:27.00000PUT FOLDER ON G DRIVE BECAUSE OTHER PLANS MUST HAVE
 BEEN HARD COPY
  
2025-06-03 08:26:53.00000LUPE@COOLANDCOBB.COM MAILED THE REVISION DIRECTLY TO
 JASON RAPER

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status D Date 05-19-2025 Cont ID  
Sent By hlopez Date 05-19-2025 Time 15:22 Rev Time 0.00
Received By hlopez Date 05-07-2025 Time 15:37 Sent To  
Notes
2025-05-19 15:23:57.00000PLAN REVIEW #: 25050230
 PROJECT: STEEL BLUE FABRICATION
 LOCATION: 780 CR 17 A
 OCCUPANCY: INDUSTRIAL
 REVIEWED BY: JASON RAPER, DIVISION CHIEF FIRE MARSHAL
 DATE: 5/19/25
 PLANS WERE REVIEWED UTILIZING THE FLORIDA FIRE
 PREVENTION CODE (FFPC), FLORIDA STATUTE, FLORIDA
 ADMINISTRATIVE RULE, AND ANY REFERENCE NFPA CODE OR
 STANDARD.
 _______________________________________________________
 _____________________
 DENIED – ONLY ONE PERMIT NUMBER (PLANS HAS BUILDING,
 SPRINKLER, AND FIRE ALARM INCLUDED)
 REVIEW FEE – $400 + INSPECTION FEE $50 = $450 BUILDING
 PLANS
 $141 + INSPECTION FEE $50 = $191 SPRINKLER PLANS
 $107 + INSPECTION FEE $50 = $157 FIRE ALARM PLANS
 BUILDING PLANS – LSC PAGE – FIRE EXTINGUISHERS ONLY
 SHOW 4 ON THE DRAWING BUT REQUIRES 6. TRAVEL DISTANCE
 TO FIRE EXTINGUISHERS IS OVER 50 FEET APART AS
 REQUIRED. EMERGENCY LIGHTS MISSING OUTSIDE DOORS AS
 REQUIRED. THE MISSING LIGHTS ARE SHOWN ON THE
 ELECTRICAL PAGES CORRECTLY. SHALL PLACE ON LSC PAGE.
 ELECTRICAL PAGES DO NOT SHOW THE EMERGENCY LIGHTS IN
 BATHROOMS AND STORAGE; HOWEVER, THEY ARE ON THE LSC
 PAGE. UPDATE THE ELECTRICAL PAGES TO SHOW THE EMERGENCY
 LIGHTS IN BATHROOMS AND STORAGE. SIDE EXIT DOOR IN
 SHOWING INSIDE OF WELDING BAY. IF ANY WALLS OF ANY TYPE
 ARE MADE TO DIVIDE THE WELDING BAYS THE SIDE EXIT DOOR
 WILL NEED TO BE OUTSIDE OF THE WELDING BAY. MECHANICAL
 PLANS IN THE NOTE SECTION HAS NFPA 101 AS 2020, SHALL
 BE 2023.
 SPRINKLER PLANS SHOW 79 UPRIGHT HEADS, BUT THE PLANS
 ONLY HAVE 76 UPRIGHT HEADS. CORRECT THE DRAWINGS FOR
 THE 79 UPRIGHT HEADS.
 FIRE ALARM – PLANS ARE GOOD