Plan Review Details - Permit 25050166
Plan Review Stops For Permit 25050166
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 4 Status A Date 07-02-2025 Cont ID  
Sent By cdorman Date 07-02-2025 Time 14:09 Rev Time 0.00
Received By cdorman Date 06-24-2025 Time 13:21 Sent To  
Notes
2025-07-02 16:10:01.00000SENT REQUEST FOR PAYMENT
2025-06-24 13:21:54.00000MONITORING@VOLTHOME.COM
 REVISION 6-23-25

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 3 Status D Date 06-18-2025 Cont ID  
Sent By cdorman Date 06-18-2025 Time 09:11 Rev Time 0.00
Received By cdorman Date 06-17-2025 Time 10:13 Sent To  
Notes
2025-06-18 09:11:28.000001] SHEET E3: THE LABEL REQUESTED PER ITEM #4 ON
 PREVIOUS REVIEW HAS NOT BEEN CORRECTLY WORDED. THE
 ONE-LINE DIAGRAM INDICATES THAT THE GATEWAY IS THE
 SERVICE DISCONNECT, THEREFORE, THE LABEL MUST BE WORDED
 "EMERGENCY DISCONNECT/SERVICE DISCONNECT" PER 230.85
 AND MUST BE AFFIXED TO THE EXTERIOR COVER OF THE
 GATEWAY.
  
 2] SHEET E3: THE DC VOLTAGE LABEL REQUESTED PER ITEM #6
 ON PREVIOUS REVIEW HAS NOT BEEN CORRECTLY COMPLETED.
 SHOW MAXIMUM DC VOLTAGE ON THIS LABEL PER 690.53 AND
 AFFIX TO EXTERIOR OF POWERWALL INVERTER. IT IS NOT
 REQUIRED TO SHOW DC CURRENT. THE COMBINED SYSTEM AC
 CURRENT IS 77 AMPS; THIS VALUE IS CORRECT FOR AC OUTPUT
 ONLY AND SHOULD BE INDICATED ON THE AC CURRENT/VOLTAGE
 LABEL REQUIRED BY 690.54, AFFIXED TO THE PV DISCONNECT.
2025-06-17 10:13:47.00000EMAILED IN FROM SOFIA.DEANGELIS@VOLTHOME.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status D Date 06-06-2025 Cont ID  
Sent By cdorman Date 06-06-2025 Time 15:17 Rev Time 0.00
Received By cdorman Date 05-16-2025 Time 12:19 Sent To  
Notes
2025-06-06 15:17:45.000001] SHEET G1: ON SUMMARY CHART, SHOW INVERTER MODEL
 NUMBER INCLUDING RATING OF 11.5 KW
 2] SHEET E1: ON SUMMARY CHART, SHOW INVERTER RATING OF
 11.5 KW
 3] SHEET E1: SHOW INSTALLATION OF SPD AT SERVICE,
 230.67 (ALTERATION OF SERVICE EQUIPMENT).
 4] SHEET E1: SHOW EMERGENCY DISCONNECT/SERVICE
 DISCONNECT LABEL ON OUTSIDE COVER OF GATEWAY, 230.85.
 ALTERNATIVELY, THIS LABEL MAY BE SHOWN ON SHEET E3.
 5] SHEET E1: REMOVE NEUTRAL/GROUND BOND IN THE 100A PV
 DISCONNECT, 250.24 (A)(5). THIS DEVICE IS ON THE LOAD
 SIDE OF THE SERVICE DISCONNECT.
 6] SHEET E3: SHOW THE CALCULATED MAXIMUM SYSTEM DC
 VOLTAGE ON A LABEL TO BE AFFIXED TO THE INVERTER,
 690.53. DO NOT SHOW DC CURRENT AS "77 AMPS".
2025-05-16 12:17:42.00000REVISION UPLOADED ON FTP SITE. EMAIL CONTACT
 SOFIA.DEANGELIS@VOLTHOME.COM AND ALSO STORED ON G DRIVE
 IN THE EMAIL APP &PLANS FOLDER

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 05-06-2025 Cont ID  
Sent By cdorman Date 05-06-2025 Time 15:07 Rev Time 0.00
Received By cdorman Date 05-06-2025 Time 09:53 Sent To  
Notes
2025-05-06 15:07:17.00000PROVIDE COMPLETE SET OF CONSTRUCTION PLANS INCLUDING:
  
 1] SYSTEM SUMMARY COVER SHEET
 2] ROOF LAYOUT
 3] ROOF STRUCTURAL ATTACHMENT SHEET
 4] FIRE PATH/SETBACK PLAN
 5] PROPERTY SITE PLAN
 6] EQUIPMENT LOCATION PLAN (PHYSICAL LOCATION ON
 STRUCTURE)
 7] ONE-LINE ELECTRICAL DIAGRAM
 8] SPECIFICATION PAGES FOR INVERTERS, MODULES,
 OPTIMIZERS (IF USED), AND OTHER MAJOR COMPONENTS
2025-05-06 09:53:26.00000EMAILED IN FROM SOFIA.DEANGELIS@VOLTHOME.COM