Plan Review Details - Permit 25040960
Plan Review Stops For Permit 25040960
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status A Date 05-12-2025 Cont ID  
Sent By amhernan Date 05-12-2025 Time 11:38 Rev Time 0.00
Received By amhernan Date 05-12-2025 Time 11:38 Sent To  
Notes
2025-10-02 12:22:04.00000SEPTIC PERMIT AND ORIGIANL APP WITH HD APPROVAL IN
 ONBASE

Review Stop ENGINEER SITE & DRAINAGE FDO
Rev No 1 Status A Date   Cont ID  
Sent By   Date 05-12-2025 Time   Rev Time  
Received By   Date 05-12-2025 Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status A Date 05-16-2025 Cont ID  
Sent By hlopez Date 05-16-2025 Time 15:40 Rev Time 0.00
Received By hlopez Date 05-12-2025 Time 11:38 Sent To  
Notes
2025-05-16 15:40:54.00000PLAN REVIEW #: 25040960
 PROJECT: HIGH GROVE RANGE BARN
 LOCATION: PRILLWITZ RD
 OCCUPANCY:
 REVIEWED BY: JASON RAPER, DIVISION CHIEF FIRE MARSHAL
 DATE: 5/15/25
 PLANS WERE REVIEWED UTILIZING THE FLORIDA FIRE
 PREVENTION CODE (FFPC), FLORIDA STATUTE, FLORIDA
 ADMINISTRATIVE RULE, AND ANY REFERENCE NFPA CODE OR
 STANDARD.
 _______________________________________________________
 _____________________
 APPROVED – WITH COMMENTS
 ADD FIRE EXTINGUISHER AS SHOWN ON PLANS
 ADD EMERGENCY LIGHTS – RISER ROOM,
 ELECTRICAL/MECHANICAL ROOM, STAIRS, CADDY AREA, STORAGE
 ROOMS, PRO SHOP, FITNESS ROOM, BAG ROOM, CORRIDOR, AND
 EXTERIOR AS SHOWN ON PLANS
 ADD EXIT/EMERGENCY COMBO LIGHTS – STAIRS, CADDY AREA,
 STORAGE ROOMS, PRO SHOP, FITNESS ROOM, BAG ROOM,
 CORRIDOR, AND EXTERIOR AS SHOWN ON PLANS
 SHALL SUBMIT PLANS FOR FIRE ALARM AND SPRINKLER SYSTEM
 NO ELECTRICAL PLANS OR MECHANICAL PLANS WERE SUBMITTED.
 SHALL SUBMIT THESE PLANS.
 2023 FLORIDA FIRE PREVENTION CODE 8TH ED – 2021 NFPA 1
 AND NFPA 101
2025-05-12 11:53:22.00000EMAILED IN FROM BRIAN@ELEV8BUILDERSLLC.COM