-     My Account  
   

Log in is not required to search. In the red banner above select: I Want To > Search > Permits

Plan Review Details - Permit 25040848
Plan Review Stops For Permit 25040848
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status A Date 05-06-2025 Cont ID  
Sent By hlopez Date 05-06-2025 Time 15:34 Rev Time 0.00
Received By hlopez Date 04-25-2025 Time 09:58 Sent To  
Notes
2025-05-06 15:34:35.00000PLAN REVIEW #: 25040848
 PROJECT: AMAZON – FIRE ALARM
 LOCATION: 1249 US 27
 OCCUPANCY: STORAGE
 REVIEWED BY: JASON RAPER, DIVISION CHIEF FIRE MARSHAL
 DATE: 5/6/25
 PLANS WERE REVIEWED UTILIZING THE FLORIDA FIRE
 PREVENTION CODE (FFPC), FLORIDA STATUTE, FLORIDA
 ADMINISTRATIVE RULE, AND ANY REFERENCE NFPA CODE OR
 STANDARD.
 _______________________________________________________
 _____________________
 APPROVED – WITH NOTES
 REVIEW FEE – $156.50 + INSPECTION FEE $50 = $206.50
 ADD MANUAL PULL STATION SHOWN ON PLANS.
 ADD HEAT DETECTOR TO THE FIRE PUMP/RISER ROOM.
 ADD TWO MORE WATER FLOW ALARMS FOR EACH RISER FOR A
 TOTAL OF 3.
 ADD DOCUMENT BOX AT FIRE ALARM PANEL
 INSPECTION OF THE ENTIRE SYSTEM ONCE COMPLETED.
2025-04-25 09:58:41.00000RAUL.GOMEZ@DYNAFIRE.COM

Copyright © 2008 – THE PLUS SERIES ® – All Rights Reserved