-     My Account  
   

Log in is not required to search. In the red banner above select: I Want To > Search > Permits

Plan Review Details - Permit 25040617
Plan Review Stops For Permit 25040617
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status C Date 05-06-2025 Cont ID  
Sent By elongsho Date 05-06-2025 Time 20:54 Rev Time 0.00
Received By elongsho Date 04-17-2025 Time 16:17 Sent To  
Notes
2025-05-12 14:42:00.00000NEEDS: SEPTIC PERMIT
2025-05-06 20:56:45.00000SHEET #8. RISER DIAGRAM NEEDS EXTERIOR DISCONNECT.
 SERVICE CONDUCTORS AND FEEDER CONDUCTORS MUST BE 4/0
 CU. EGC MUST BE #4 CU.

Review Stop ENGINEER SITE & DRAINAGE FDO
Rev No 1 Status A Date 05-12-2025 Cont ID  
Sent By cshackel Date 05-12-2025 Time 14:40 Rev Time 0.00
Received By cshackel Date 04-17-2025 Time 14:40 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status A Date 05-05-2025 Cont ID  
Sent By hlopez Date 05-05-2025 Time 16:16 Rev Time 0.00
Received By hlopez Date 04-17-2025 Time 16:16 Sent To  
Notes
2025-05-05 16:17:06.00000PLAN REVIEW #: 25040617
 PROJECT: GLADES ELECTRIC
 LOCATION: 214 SR 70
 OCCUPANCY:
 REVIEWED BY: JASON RAPER, DIVISION CHIEF FIRE MARSHAL
 DATE: 5/5/2025
 PLANS WERE REVIEWED UTILIZING THE FLORIDA FIRE
 PREVENTION CODE (FFPC), FLORIDA STATUTE, FLORIDA
 ADMINISTRATIVE RULE, AND ANY REFERENCE NFPA CODE OR
 STANDARD.
 _______________________________________________________
 _____________________
 APPROVED –
 REVIEW FEE – $400 + INSPECTION FEE $50 = $450
 WATER TANK SHALL HAVE 6” STANDARD THREADS FOR FIRE
 DEPARTMENT CONNECTION

Copyright © 2008 – THE PLUS SERIES ® – All Rights Reserved