-     My Account  
   

Log in is not required to search. In the red banner above select: I Want To > Search > Permits

Plan Review Details - Permit 25030846
Plan Review Stops For Permit 25030846
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status A Date 04-22-2025 Cont ID  
Sent By cdorman Date 04-22-2025 Time 15:47 Rev Time 0.00
Received By cdorman Date 04-08-2025 Time 13:52 Sent To  
Notes
2025-04-23 08:44:25.00000SENT REQUEST FOR PAYMENT
2025-04-08 13:53:15.00000CORRECT PLANS PERMITSARASOTA@FREEDOMFOREVER.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 03-27-2025 Cont ID  
Sent By cdorman Date 03-27-2025 Time 13:35 Rev Time 0.00
Received By cdorman Date 03-27-2025 Time 11:22 Sent To  
Notes
2025-03-27 13:34:56.00000SHEET PV-4: SHOW CONDUCTORS BETWEEN PV DISCONNECT AND
 SUPPLY SIDE TAP AS (3) #6 CU THWN. NOTE THAT AN
 EQUIPMENT GROUNDING CONDUCTOR IS NOT INSTALLED IN THIS
 CONDUIT BECAUSE THE SYSTEM IS BONDED TO GROUND IN THE
 PV DISCONNECT VIA THE NEUTRAL. REFERENCE 250.25 (A),
 705.11 (B), & TBL. 310.16.
2025-03-27 11:22:45.00000PERMITSARASOTA@FREEDOMFOREVER.COM
 NOC: OR BK 3105 PG 1370 [IN ONBASE]

Copyright © 2008 – THE PLUS SERIES ® – All Rights Reserved