-     My Account  
   

Log in is not required to search. In the red banner above select: I Want To > Search > Permits

Plan Review Details - Permit 25030672
Plan Review Stops For Permit 25030672
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 03-24-2025 Cont ID  
Sent By cdorman Date 03-24-2025 Time 12:07 Rev Time 0.00
Received By cdorman Date 03-24-2025 Time 08:42 Sent To  
Notes
2025-03-24 12:07:12.00000SHEET PV-4: EQUIPMENT GROUNDING CONDUCTOR BETWEEN
 BACKUP INTERFACE AND BACKUP LOAD CENTER MUST BE MINIMUM
 #6 CU.
2025-03-24 08:43:08.00000PERMITSARASOTA@FREEDOMFOREVER.COM