Plan Review Details - Permit 25020864
Plan Review Stops For Permit 25020864
Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status A Date 03-31-2025 Cont ID  
Sent By hlopez Date 03-31-2025 Time 12:51 Rev Time 0.00
Received By hlopez Date 03-25-2025 Time 10:40 Sent To  
Notes
2025-03-31 12:52:28.00000INSPECTIONS REQUIRED ROUGH IN, PUMP BREAKIN/TEST,
 PRESSURE TEST, FLOW TEST
2025-03-25 10:41:59.00000REC'D BY FEDEX - EMAILING JASON TO COME PICK UP

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status D Date 03-18-2025 Cont ID  
Sent By hlopez Date 03-18-2025 Time 12:39 Rev Time 0.00
Received By hlopez Date 03-14-2025 Time 11:19 Sent To  
Notes
2025-03-18 12:39:45.00000 
 PLAN REVIEW #: 25020864
 PROJECT: AMAZON RSR (WFL6) SPRINKLER SYSTEM WITH FIRE
 PUMP
 LOCATION: 1249 US 27, LAKE PLACID
 OCCUPANCY: STORAGE
 REVIEWED BY: JASON RAPER, DIVISION CHIEF FIRE MARSHAL
  
 DATE: 3/1/25
  
 PLANS WERE REVIEWED UTILIZING THE FLORIDA FIRE
 PREVENTION CODE (FFPC), FLORIDA STATUTE, FLORIDA
 ADMINISTRATIVE RULE, AND ANY REFERENCE NFPA CODE OR
 STANDARD.
 _______________________________________________________
 _____________________
 DENIED
  
 • FDC LINE IS SHOWN TO CONNECT TO THE CANOPY BRANCH
 OUTSIDE OF THE PUMP ROOM. FDC LINE SHALL BE CONNECTED
 TO THE MAIN LINE INSIDE THE PUMP ROOM FOR ALL THE
 BRANCHES BEHIND THE PUMP. THE CONNECTION SHALL NOT GO
 INTO THE PUMP ON THE SUPPLY SIDE.
 • SHALL ADD FIRE DEPARTMENT HOSE CONNECTIONS AT ALL
 EXIT DOORS AS INDICATED ON THE PLANS PAGE FP7.0. SHALL
 BE OFF THE 4” BRANCH FOR 5 OF THE CONNECTIONS AND 2 OF
 THE CONNECTIONS WILL HAVE TO COME OFF THE 2 ½” BRANCH
 LINE. THESE CONNECTIONS SHALL NOT COME OFF ANY LINES
 SMALLER THAN THE 2 ½” BRANCH LINES.
 • FP2.0 DOES NOT MATCH FP7.0 WITH THE MAIN BRANCH LINE
 COMING FROM PUMP ROOM.
 • FP2.0 DOES NOT SHOW THE OFFICE LAYOUT AS IT DOES ON
 FP7.0
 • FP2.0 SHOWS THE WAREHOUSE HEADS ONLY IT SHOULD SHOW
 THE OFFICE AREA WITH THE MENTION THAT THIS IS THE COVER
 ABOVE THE OFFICE AREA.
 • FP7.0 SHOULD SHOW ALL THE HEADS FOR THE ENTIRE
 PROJECT. THIS SHOULD ALSO BE CORRECT ON THE MAIN BRANCH
 LINES FOR THE PROJECT.
 • PLANS ALSO SHOWS ADDRESS AS 1251 US 27 ALL OTHER
 SUBMISSIONS HAVE BEEN 1249 US 27.
  
 REVIEW FEE – $624 + INSPECTION FEE $100 = $724
  
2025-03-14 11:20:16.00000FEDEX PLANS REC'D - CALLED JASON TO PICK UP

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status R Date   Cont ID  
Sent By   Date 03-13-2025 Time   Rev Time 0.00
Received By cshackel Date 02-27-2025 Time 13:33 Sent To  
Notes
2025-03-13 10:57:25.00000JASON ASKED THAT THEY PROVIDE A FULL SIZE SET OF PLANS
 AND ALL BREAKOUT PAGES TOGETHER
2025-03-04 09:06:09.00000SENT FDC SUPPLY LINE PLAN 3/4/25
 IGANDEN@CHASOLUTIONS.COM
2025-02-27 13:39:23.00000IGANDEN@CHASOLUTIONS.COM