-     My Account  
   

Log in is not required to search. In the red banner above select: I Want To > Search > Permits

Plan Review Details - Permit 25020843
Plan Review Stops For Permit 25020843
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 4 Status A Date 06-05-2025 Cont ID  
Sent By cdorman Date 06-05-2025 Time 08:45 Rev Time 0.00
Received By cdorman Date 06-05-2025 Time 08:45 Sent To  
Notes
2025-06-09 09:33:30.00000SENT REQUEST FOR PAYMENT

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 3 Status R Date 05-29-2025 Cont ID  
Sent By cdorman Date 05-29-2025 Time 13:12 Rev Time 0.00
Received By cdorman Date 05-29-2025 Time 11:25 Sent To  
Notes
2025-05-29 13:12:56.00000PROVIDE STATEMENT OF VALUATION. VALUATION MAY HAVE
 CHANGED DUE TO THE ADDITION OF NEW MPU.
2025-05-29 11:26:10.00000PERMITSARASOTA@FREEDOMFOREVER.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status A Date 04-17-2025 Cont ID  
Sent By cdorman Date 04-17-2025 Time 14:19 Rev Time 0.00
Received By cdorman Date 04-09-2025 Time 09:38 Sent To  
Notes
2025-04-23 08:12:27.00000SENT REQUEST FOR PAYMENT
2025-04-09 09:39:20.00000REVISED PER EXAMINER COMMENTS
 PERMITSARASOTA@FREEDOMFOREVER.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 02-27-2025 Cont ID  
Sent By cdorman Date 02-27-2025 Time 12:41 Rev Time 0.00
Received By cdorman Date 02-26-2025 Time 15:32 Sent To  
Notes
2025-03-04 16:17:55.00000EMAILED 4:17 PM 3/4/2025 CAS
2025-02-27 12:41:03.00000SHEET PV4: CLARIFY INTERCONNECTION METHOD IN MSP. A
 "LUG KIT" IS SPECIFIED AS A TERMINATION ON THE EXISTING
 100A SUBPANEL FEEDERS; THE SPECIFIED CONNECTION METHOD
 IS UNCLEAR.
 IF USING A FEEDER TAP, SHOW FEEDER CONDUCTOR SIZE AND
 OVERCURRENT PROTECTION ON THE LOAD END OF THE FEEDER
 (I.E., A MAIN BREAKER IN THE EXISTING SUBPANEL). FEEDER
 TAPS MUST COMPLY WITH 705.12 (B).
 IF USING A BUS CONNECTION, SHOW SERVICE DISCONNECT IN
 MSP.
2025-02-26 15:32:29.00000PERMITSARASOTA@FREEDOMFOREVER.COM