Plan Review Details - Permit 25010804
Plan Review Stops For Permit 25010804
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status A Date 04-29-2025 Cont ID  
Sent By elongsho Date 04-29-2025 Time 16:56 Rev Time 0.00
Received By elongsho Date 01-23-2025 Time 09:22 Sent To  
Notes
2025-01-23 09:47:01.00000YURI.RAMIREZ@JOHNSONGROUP.GLOBAL
  

Review Stop ENGINEER SITE & DRAINAGE FDO
Rev No 1 Status A Date 02-03-2025 Cont ID  
Sent By cshackel Date 02-03-2025 Time 15:01 Rev Time 0.00
Received By cshackel Date 02-03-2025 Time 15:01 Sent To  
Notes
2025-02-03 15:02:20.00000CONDITION SITE PLAN EXEMPTION, WILL NEED FINAL RELEASE
 BEFORE CO.... ENG# 24020019

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status A Date 04-24-2025 Cont ID  
Sent By hlopez Date 04-24-2025 Time 15:30 Rev Time 0.00
Received By hlopez Date 04-07-2025 Time 15:30 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status D Date 03-07-2025 Cont ID  
Sent By hlopez Date 03-07-2025 Time 07:55 Rev Time 0.00
Received By hlopez Date 02-10-2025 Time 10:49 Sent To  
Notes
2025-03-07 07:57:31.00000PLAN REVIEW#: 25010804
 PROJECT: ARCHBOLD CHEMISTRY LAB REMODEL LOCATION: 123
 MAIN DR, VENUS, FL OCCUPANCY:
 REVIEWED BY: JASON RAPER, DIVISION CHIEF FIRE MARSHAL
 DATE: 3/6/2025
 PLANS WERE REVIEWED UTILIZING THE FLORIDA FIRE
 PREVENTION CODE (FFPC), FLORIDA STATUTE, FLORIDA
 ADMINISTRATIVE RULE, AND ANY REFERENCE NFPA CODE OR
 STANDARD.
  
 DENIED
 COMMENT #1 - PLANS DO NOT SHOW FDC LOCATION FOR
 SPRINKLER SYSTEM, RISER LOCATION FOR SPRINKLER SYSTEM,
 OR FIRE LINE.
 RESPONSE: ONLY THE "CHEMICAL LABORATORY UNIT" REQUIRES
 FIRE SUPPRESSION PER NFPA 45. THE REMAINDER OF THE
 LABORATORY FALLS UNDER NFPA 1.1.3(1)(A), AS ALL
 QUANTITIES OF HAZARDOUS AND/OR FLAMMABLE LIQUIDS ARE
 RESTRICTED TO THE "CHEMICAL LABORATORY UNIT."
 A DRY CHEMICAL SUPPRESSION SYSTEM INSTALLED IN
 ACCORDANCE WITH NFPA 17 HAS BEEN SPECIFIED TO BE
 INSTALLED IN THE "CHEMICAL LABORATORY UNIT," AS NOTED
 PER NFPA 45
 6.1.2.2. THIS LABORATORY UNIT HAS BEEN SEPARATED FROM
 THE REMAINDER OF THE LABORATORY WITH A I-HOUR FIRE
 SEPARATION PER THE TABLE 5.1.1 IN NFPA 45.
 ADDED NOTE TO PAGE 4 FOR CLARITY.
 A.6.1.2 THE BASIC PHILOSOPHY OF NFPA 45 IS TO PROTECT
 LABORATORY WORK AREAS WITH SPRINKLERS IN ACCORDANCE
 WITH NFPA 13. IF A HAZARD ASSESSMENT SHOWS THAT THE
 PRESENCE OF WATER-REACTIVE MATERIALS WOULD CREATE A
 SERIOUS FIRE OR PERSONNEL HAZARD IN THE EVENT OF THE
 DISCHARGE OF SPRINKLER WATER, A NONWATER AUTOMATIC FIRE
 EXTINGUISHING SYSTEM DESIGNED TO PROTECT THE PORTION OF
 THE LAB WORK AREA CONTAINING WATER-REACTIVE MATERIALS
 IS ACCEPTABLE. NFPA 45-6.1.2.1 WHERE WATER WILL CREATE
 A SERIOUS FIRE OR PERSONNEL HAZARD, A SUITABLE NONWATER
 AUTOMATIC EXTINGUISHING SYSTEM SHALL BE PERMITTED TO BE
 AN ACCEPTABLE SUBSTITUTE FOR SPRINKLERS.
 THIS CODE IS USED IF THE WATER FROM THE SPRINKLER
 SYSTEM WOULD CREATE A SERIOUS FIRE OR PERSONNEL HAZARD.
 SEE IF THE ITEMS ARE WATER REACTIVE IN THE LAB?
 REVIEW FEE - $100 + INSPECTION FEE $50 = $150
  
2025-02-10 10:49:34.00000REVISED DRAWINGS WITH CORRECTIONS AND RESPONSES
 FORWARDED TO JASON RAPER

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status D Date 01-28-2025 Cont ID  
Sent By hlopez Date 01-28-2025 Time 11:16 Rev Time 0.00
Received By hlopez Date 01-23-2025 Time 09:22 Sent To  
Notes
2025-01-28 11:16:59.00000PLAN REVIEW #: 25010804
  
 PROJECT: ARCHBOLD CHEMISTRY LAB REMODEL
  
 LOCATION: 123 MAIN DR, VENUS, FL
  
 OCCUPANCY:
  
 REVIEWED BY: JASON RAPER, DIVISION CHIEF FIRE MARSHAL
  
 DATE: 1/28/25
  
 PLANS WERE REVIEWED UTILIZING THE FLORIDA FIRE
 PREVENTION CODE (FFPC), FLORIDA STATUTE, FLORIDA
 ADMINISTRATIVE RULE, AND ANY REFERENCE NFPA CODE OR
 STANDARD.
 _______________________________________________________
 _____________________
 DENIED –
  
 • PLANS DO NOT SHOW FDC LOCATION FOR SPRINKLER SYSTEM,
 RISER LOCATION FOR SPRINKLER SYSTEM, OR FIRE LINE.
 • PLANS INDICATE FIRE ALARM NOT REQUIRED. BUILDING HAS
 FIRE ALARM ALREADY – WILL REQUIRE TO UPDATE IN THIS
 AREA. PLUS, THE SPRINKLERS SYSTEM WILL BE REQUIRED TO
 BE HOOKED TO THE FIRE ALARM SYSTEM. (TAMPER AND FLOW
 ALARMS)
 • LIFE SAFETY PLANS – FIRE EXTINGUISHERS CHANGE SEE
 PLANS – ELECTRICAL PLANS SHOW EXIT INTO HALLWAY BUT NOT
 ON THE LIFE SAFETY PLAN PLUS THOSE DOORS SWING INTO THE
 LAB NOT THE HALL
 • ELECTRICAL PLANS – DO NOT SHOW THE EMERGENCY LIGHTS
 THAT MATCH THE LIFE SAFETY PLAN
  
 • WILL REQUIRE PLANS FOR THE SPRINKLER SYSTEM AND
 UPDATED FIRE ALARM PLANS
  
 REVIEW FEE – $100 + INSPECTION FEE $50 = $150
  
  
 ... PLEASE BE ADVISED THIS REVIEW OF PLANS SUBMITTED IS
 A CURSORY REVIEW TO ASSIST THE CONTRACTOR IN COMPLIANCE
 WITH APPLICABLE FIRE SAFETY CODES. THIS REVIEW IS NOT
 INTENDED TO BE A FINAL APPROVAL OF THE SUBMITTED PLANS.
 IT IS THE CONTRACTOR'S SOLE RESPONSIBILITY TO ENSURE
 THAT THE PLANS ARE IN COMPLETE COMPLIANCE WITH ALL
 APPLICABLE NFPA CODES STATE STATUTES AND LOCAL
 ORDINANCE. IN THE EVENT THAT FURTHER EXAMINATION OR
 SITE INSPECTION REVEALS AREAS OF NON-COMPLIANCE. IT
 SHALL BE THE CONTRACTOR'S SOLE RESPONSIBILITY, AT THEIR
 SOLE EXPENSE TO BRING THOSE AREAS IN COMPLIANCE. FIRE
 MARSHAL’S OFFICE ASSUMES NO RESPONSIBILITY FOR THE
 CONTRACTOR'S FAILURE TO BE IN COMPLIANCE WITH ALL
 APPLICABLE NFPA CODES, STATE STATUTES AND LOCAL
 ORDINANCES.
  

Review Stop ZONING ZONING DEPARTMENT
Rev No 1 Status X Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By cshackel Date 01-23-2025 Time 09:22 Sent To  
Notes
***NONE***