Plan Review Details - Permit 25010797
Plan Review Stops For Permit 25010797
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 3 Status A Date 04-03-2025 Cont ID  
Sent By cdorman Date 04-03-2025 Time 14:51 Rev Time 0.00
Received By cdorman Date 03-25-2025 Time 08:13 Sent To  
Notes
***NONE***

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status A Date 02-05-2025 Cont ID  
Sent By cdorman Date 02-05-2025 Time 13:58 Rev Time 0.00
Received By cdorman Date 01-28-2025 Time 13:57 Sent To  
Notes
2025-02-18 09:39:20.00000SENT REQUEST FOR PAYMENT

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 01-23-2025 Cont ID  
Sent By cdorman Date 01-23-2025 Time 11:18 Rev Time 0.00
Received By cdorman Date 01-23-2025 Time 08:43 Sent To  
Notes
2025-01-23 11:18:34.00000SHEET PV-4:
 1] CONDUCTORS SUPPLYING 150A BACKUP LOAD CENTER ARE
 UNDERSIZED
 2] 80A PV BREAKER IN EXISTING SERVICE PANEL, BASED ON
 GIVEN INFORMATION, DOES NOT COMPLY WITH 705.12 (B)(3)
 3] CONDUCTORS ON LINE AND LOAD SIDES OF TWO KNIFE-BLADE
 SAFETY SWITCHES MAY BE MIS-IDENTIFIED; THESE SWITCHES
 WILL NOT PROVIDE ADEQUATE GUTTER SPACE FOR THESE
 CONDUCTORS, AND MAY NOT INCORPORATE LUGS SUFFICIENT FOR
 250 KCMIL AWG. CORRECT CONDUCTOR SIZES AS NECESSARY.
  
 SHEET PV-7: THE VALUE SHOWN ON THE AC CURRENT LABEL IS
 INCORRECT.
2025-01-23 08:44:04.00000PERMITSARASOTA@FREEDOMFOREVER.COM