-     My Account  
   

Log in is not required to search. In the red banner above select: I Want To > Search > Permits

Plan Review Details - Permit 25010791
Plan Review Stops For Permit 25010791
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status C Date 05-22-2025 Cont ID  
Sent By hlopez Date 05-22-2025 Time 09:45 Rev Time 0.00
Received By hlopez Date 01-22-2025 Time 16:13 Sent To  
Notes
2025-05-22 09:46:03.00000MUST HAVE SECONDARY MEANS OF EGRESS OUT OF BEDROOMS ON
 UPPER FLOOR
2025-01-22 16:13:50.00000MEGANL@BUILD-GH.COM

Review Stop ENGINEER SITE & DRAINAGE FDO
Rev No 1 Status A Date 01-22-2025 Cont ID  
Sent By hlopez Date 01-22-2025 Time 16:13 Rev Time 0.00
Received By hlopez Date 01-22-2025 Time 16:13 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status A Date 04-16-2025 Cont ID  
Sent By hlopez Date 04-16-2025 Time 11:25 Rev Time 0.00
Received By hlopez Date 04-01-2025 Time 08:18 Sent To  
Notes
2025-04-16 11:26:33.00000PLAN REVIEW #:
 25010791/25010790/25010787/25010775/25010777/25010772
 PROJECT: APEX GARAGES TOWNHOMES
 LOCATION: COZUMEL LN
 OCCUPANCY:
 REVIEWED BY: JASON RAPER, DIVISION CHIEF FIRE MARSHAL
 DATE: 4/16/25
 PLANS WERE REVIEWED UTILIZING THE FLORIDA FIRE
 PREVENTION CODE (FFPC), FLORIDA STATUTE, FLORIDA
 ADMINISTRATIVE RULE, AND ANY REFERENCE NFPA CODE OR
 STANDARD.
 _______________________________________________________
 _____________________
 APPROVED – WITH COMMENTS
 A0.4 – COMMON PATH DISTANCE
 A0.5 – TRAVEL DISTANCE IS MEASURED 12” OFF WALL AND
 OBJECTS
 A2.1 – W3/W4/W5 SHOULD HAVE BEEN CLOUDED SINCE THEY
 WERE CHANGED TO CASEMENT WINDOW AS
 SHOWN ON A8.0
 A2.1 – W8/W/9 IS CLOUDED BUT ON A8.0 THEY WERE NOT
 CLOUDED – WAS THIS A MISTAKE
 A3.1 – CO/SMOKE DETECTOR IS MISSING IN HALLWAY OUTSIDE
 BEDROOM #3
2025-04-01 08:18:49.00000REVISED PLANS RECEIVED JORGEC@BUILD-GH.COM

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status D Date 02-26-2025 Cont ID  
Sent By hlopez Date 02-26-2025 Time 11:21 Rev Time 0.00
Received By hlopez Date 01-22-2025 Time 16:14 Sent To  
Notes
2025-02-26 11:21:55.00000REFERENCE #: 25010791- BLD 6, 25010790 - BLD 5,
 25010787 - BLD 4, 25010777 - BLD 2, 25010775 - BLD 3,
 25010722 - BLD 1
  
 PROJECT: APEX TOWNHOUSES BLD 6, BLD 5, BLD 4, BLD 2,
 BLD 3, BLD 1
  
 LOCATION: 8150 - BLD 6, 8148 - BLD 5, 8146 - BLD 4,
 8142 - BLD 2, 8144 - BLD 3, 8140 COZUMIEL LANE - BLD 1
  
 CONTRACTOR:
  
 OCCUPANCY: TOWNHOUSES
  
 REVIEWED BY: JASON RAPER, DIVISION CHIEF FIRE MARSHAL
  
 PLANS WERE REVIEWED UTILIZING THE FLORIDA FIRE
 PREVENTION CODE (FFPC), FLORIDA STATUTE, FLORIDA
 ADMINISTRATIVE RULE, AND ANY REFERENCE NFPA CODE OR
 STANDARD.
 _______________________________________________________
 _____________________
  
 DENIED
  
 LIFE SAFETY PLANS NEED TO SHOW TRAVEL DISTANCES FROM
 ALL BEDROOMS.
 SECOND MEANS OF EGRESS FROM BEDROOMS AS REQUIRED BY FBC
 2021 IN SECTION 1030 EMERGENCY ESCAPE AND RESCUE. ALL
 WINDOWS IN SCHEDULE SHOW FIXED WINDOWS.
 ELECTRICAL PLANS DO NOT SHOW SMOKE OR CO DETECTORS
  
 REVIEW FEE – $400 + INSPECTION FEE $50 = $450
  

Copyright © 2008 – THE PLUS SERIES ® – All Rights Reserved