Plan Review Details - Permit 25010748
Plan Review Stops For Permit 25010748
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 5 Status A Date 06-25-2025 Cont ID  
Sent By cdorman Date 06-25-2025 Time 16:10 Rev Time 0.00
Received By cdorman Date 06-17-2025 Time 07:51 Sent To  
Notes
2025-06-17 07:51:13.00000REVISED PLANS

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 4 Status A Date 04-08-2025 Cont ID  
Sent By cdorman Date 03-11-2025 Time   Rev Time 0.00
Received By cdorman Date 03-06-2025 Time 10:37 Sent To  
Notes
2025-03-06 10:37:59.00000REVISIION, PERMITSARASOTA@FREEDOMFOREVER.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 3 Status A Date 02-19-2025 Cont ID  
Sent By cdorman Date 02-19-2025 Time 12:12 Rev Time 0.00
Received By cdorman Date 02-07-2025 Time 15:35 Sent To  
Notes
2025-02-24 11:42:50.00000SENT REQUEST FOR PAYMENT
2025-02-07 15:35:51.00000PERMITSARASOTA@FREEDOMFOREVER.COM
  

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status D Date 02-04-2025 Cont ID  
Sent By cdorman Date 02-04-2025 Time 09:28 Rev Time 0.00
Received By cdorman Date 01-30-2025 Time 11:12 Sent To  
Notes
2025-02-04 09:28:52.00000SHEET PV-4:
 1] SHOW CORRECT SIZE OF EXISTING SYSTEM STRING INVERTER
 (OR MICROINVERTERS, IF PRESENT). "SOLAREDGE 440W" IS
 INACCURATE.
 2] THERE ARE TWO DIFFERENT CALLOUTS SHOWN ON THE
 CONDUCTORS BETWEEN THE NEW 3.8 KW STRING INVERTER AND
 THE 60A DISCONNECT. SHOW ONLY ONE CORRECT CONDUCTOR
 SIZE.
  
2025-01-30 11:13:56.00000PERMITSARASOTA@FREEDOMFOREVER.COM
 NOC OR BK 3093 PG 657 [ON BASE]

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 01-22-2025 Cont ID  
Sent By cdorman Date 01-22-2025 Time 16:27 Rev Time 0.00
Received By cdorman Date 01-22-2025 Time 09:03 Sent To  
Notes
2025-01-22 16:27:53.00000SHEET PV-4:
 1] SHOW SIZE OF STRING INVERTER ON EXISTING SYSTEM
 2] THERE ARE TWO DIFFERENT CONDUCTOR IDENTIFICATION
 LABELS SHOWN ON THE CONDUCTORS BETWEEN THE NEW 3.8 KW
 INVERTER AND THE 60A DISCONNECT. SHOW ONLY ONE CORRECT
 CONDUCTOR SIZE.
 3] A BACKFED 100A PV BREAKER IS INDICATED IN THE
 EXISTING 200A-RATED MAIN SERVICE PANEL. THE COMBINED
 RATING OF ALL BREAKERS IN THIS PANEL (EXCEPT UTILITY
 MAIN) MUST NOT EXCEED THE RATING OF THE BUSBAR AND
 PROPER LABELING IS REQUIRED FOR THIS CONDITION PER
 705.12 (B)(3)(3).
 ALTERNATIVELY, USE A DIFFERENT METHOD OF
 INTERCONNECTION.
2025-01-22 09:04:34.00000PERMITSARASOTA@FREEDOMFOREVER.COM