Plan Review Details - Permit 25010375
Plan Review Stops For Permit 25010375
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status A Date 01-29-2025 Cont ID  
Sent By cdorman Date 01-29-2025 Time 17:04 Rev Time 0.00
Received By cdorman Date 01-24-2025 Time 16:45 Sent To  
Notes
2025-02-18 09:43:22.00000SENT REQUEST FOR PAYMENT
2025-01-24 16:45:46.00000O.GONZALEZ@WINDMARHOME.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 01-10-2025 Cont ID  
Sent By cdorman Date 01-10-2025 Time 14:05 Rev Time 0.00
Received By cdorman Date 01-10-2025 Time 13:21 Sent To  
Notes
2025-01-10 14:05:18.000001] SHEET L1: PER 690.54, SHOW AN AC CURRENT/VOLTAGE
 LABEL TO BE AFFIXED TO THE GATEWAY INDICATING THE TOTAL
 COMBINED SYSTEM OUTPUT (BOTH INVERTERS COMBINED). THIS
 REQUIREMENT DOES NOT PROHIBIT AFFIXING SEPARATE AC
 CURRENT/VOLTAGE LABELS TO EACH INVERTER INDICATING THE
 OUTPUT OF EACH.
 2] SHEET D7: CHANGE THE IDENTIFIER ON THE GATEWAY IN
 THE DIAGRAM TO A "GATEWAY 3" TO AGREE WITH THE
 EQUIPMENT SCHEDULE ON SHEET E1.