Plan Review Stops For Permit 24120604
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status A Date 01-09-2025 Cont ID  
Sent By cdorman Date 01-09-2025 Time 15:50 Rev Time 0.00
Received By cdorman Date 12-27-2024 Time 12:20 Sent To  
Notes
2025-01-10 12:16:21.00000SENT REQUEST FOR PAYMENT
2024-12-27 12:21:18.00000EMAILED IN FROM PERMITSARASOTA@FREEDOMFOREVER.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 12-18-2024 Cont ID  
Sent By cdorman Date 12-18-2024 Time 14:24 Rev Time 0.00
Received By cdorman Date 12-18-2024 Time 08:57 Sent To  
Notes
2024-12-18 14:24:08.00000SHEET PV-4: SUPPLY-SIDE CONDUCTORS MUST BE MINIMUM #6
 CU AND NOT INCLUDE AN EQUIPMENT GROUNDING CONDUCTOR,
 705.10 (B).
2024-12-18 08:57:32.00000PERMITSARASOTA@FREEDOMFOREVER.COM
  