Plan Review Stops For Permit 24120582
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status A Date 01-08-2025 Cont ID  
Sent By cshackel Date 01-08-2025 Time 15:59 Rev Time 0.00
Received By cshackel Date 12-17-2024 Time 14:38 Sent To  
Notes
2025-01-08 16:07:07.00000PLAN REVIEW#: 24120582
 PROJECT: STORAGE UNITS
 LOCATION: 901 US 27
 OCCUPANCY: STORAGE
 REVIEWED BY: JASON RAPER, DIVISION CHIEF FIRE MARSHALP.
 DATE: 1/2/25
 PLANS WERE REVIEWED UTILIZING THE FLORIDA FIRE
 PREVENTION CODE (FFPC), FLORIDA STATUTE, FLORIDA
 ADMINISTRATIVE RULE, AND ANY REFERENCE NFPA CODE OR
 STANDARD.
 APPROVED - WITH NOTES
 PULL STATION NEEDS TO BE ADDED TO SALES OFFICE EXIT
 DOOR
 HORN/STROBE NEEDS TO BE ADDED TO SALES OFFICE AREA
 HORN/STROBE IN BREAKROOM CHANGED TO STROBE
 DETECTORS (SMOKE OR HEAT) NEEDED IN THE ELECTRICAL
 ROOM, OFFICE STORAGE ROOM, AND FIRE RISER ROOM.
 REVIEW FEE - $155.50 + INSPECTION FEE $50 = $205.50
2024-12-17 14:43:54.00000NOC: OR BK 3051 PG 1856 [ONBASE]
2024-12-17 14:40:14.00000RAUL.GOMEZ@DYNAFIRE.COM