Plan Review Details - Permit 24120307
Plan Review Stops For Permit 24120307
Review Stop BUILDING BUILDING DEPARTMENT
Rev No 3 Status A Date 01-09-2025 Cont ID  
Sent By cdorman Date 01-09-2025 Time 15:50 Rev Time 0.00
Received By cdorman Date 12-30-2024 Time 16:15 Sent To  
Notes
2025-01-10 12:24:09.00000SET FOR PAYMENT
2024-12-30 16:15:47.00000PERMITSARASOTA@FREEDOMFOREVER.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 2 Status D Date 12-26-2024 Cont ID  
Sent By cdorman Date 12-26-2024 Time 09:05 Rev Time 0.00
Received By cdorman Date 12-26-2024 Time 07:53 Sent To  
Notes
2024-12-26 09:05:03.00000SHEET PV-4: SHOW SIZE OF OVERCURRENT PROTECTION
 SUPPLYING NEW MAIN LUG PANEL (BREAKER IN MAIN SERVICE
 PANEL) OR INDICATE IF FEED THROUGH LUGS. SHOW FEEDER
 CONDUCTOR SIZE BETWEEN MAIN SERVICE PANEL AND NEW MAIN
 LUG PANEL.
2024-12-26 07:53:34.00000REVISED PLANS PERMITSARASOTA@FREEDOMFOREVER.COM

Review Stop BUILDING BUILDING DEPARTMENT
Rev No 1 Status D Date 12-10-2024 Cont ID  
Sent By cdorman Date 12-10-2024 Time 16:10 Rev Time 0.00
Received By cdorman Date 12-10-2024 Time 09:09 Sent To  
Notes
2024-12-26 07:51:57.00000OR BK 3086 PG 1813 IN ONBASE
2024-12-10 16:10:14.00000SHEET PV4: 125% OF INVERTER OUTPUT PLUS RATING OF
 OVERCURRENT DEVICE PROTECTING THE BUSBAR EXCEEDS 120%
 OF THE BUSBAR RATING. (47.5 X 1.25) + 200 = 259A. 200 X
 1.2 = 240A.
 SEE 705.12 (B)(3)(2).
2024-12-10 09:11:06.00000PERMITSARASOTA@FREEDOMFOREVER.COM